Sanyo W-3WAY ECO-i 85464369098000 Installation Instructions Manual

W-3way eco-i system air conditioner
Table of Contents

Advertisement

R410A Models
Indoor Units
X
4-Way Air Discharge Semi-Concealed Type
XM
4-Way Air Discharge Semi-Concealed Type
A
1-Way Air Discharge Semi-Concealed Type
U
Concealed Duct Type
Concealed Duct
D
High-Static Pressure Type
T
Ceiling-Mounted Type
K
Wall-Mounted Type
Outdoor Units
C
ECO-i W-3WAY
* Refrigerant R410A is used in the outdoor units.
Optional Controllers
Timer Wired Remote Controller
Wireless Remote Controller (For U, D Types)
Wireless Remote Controller (For X Type)
Wireless Remote Controller (For XM Type)
Wireless Remote Controller (For A, T Types)
RC Wireless Remote Controller (For K Type)
Simplified Remote Controller
System Controller
Intelligent Controller
Communication Adaptor
Remote Sensor
LonWorks Interface
85464369098000 ©SANYO 2008
W-3WAY_ECO-i_US.indd a
W-3WAY_ECO-i_US.indd a
INSTALLATION INSTRUCTIONS
– W-3WAY ECO-i System Air Conditioner –
for Refrigerant R410A
This air conditioner uses the new refrigerant R410A.
External diameter of service port R410A: 5/16"
NOTE
Class
7
AHX0752
UHX0752
KHX0752
Class
90
CHDZ09053
CHDZR09053 CHDZR14053
RCS-TM80BG
RCS-BH80AAB.WL
RCS-SH80AAB.WL
RCS-XM18AAB.WL
RCS-TRP80AAB.WL
RCS-SH1AAB
RCS-KR1AGB
SHA-KC64UG
SHA-KT256BA
SHA-KA128AAB
ART-K45AGB
SHA-LN16UAB
9
12
18
XHX1252
XHX1852
XMHX1252 XMHX1852
AHX0952
AHX1252
UHX1252
UHX1852
THX1252
THX1852
KHX0952
KHX1252
KHX1852
140
CHDZ14053
SANYO Commercial Solutions
A division of SANYO North America Corporation
Cornerstone Business Park
1062 Thorndale Avenue
Bensenville, IL 60106, U.S.A.
a
24
36
48
XHX2452
XHX3652
UHX2452
UHX3652
DHX3652
DHX4852
THX2452
KHX2452
In Canada
SANYO Canada Inc.
1-300 Applewood Crescent
Concord, Ontario
L4K 5C7, Canada
2008/02/07 10:55:34
2008/02/07 10:55:34
X
XM
A
U
D
T
K

Advertisement

Table of Contents
loading

Summary of Contents for Sanyo W-3WAY ECO-i 85464369098000

  • Page 1 RCS-BH80AAB.WL RCS-SH80AAB.WL RCS-XM18AAB.WL RCS-TRP80AAB.WL RCS-SH1AAB RCS-KR1AGB SHA-KC64UG SHA-KT256BA SHA-KA128AAB ART-K45AGB SHA-LN16UAB SANYO Commercial Solutions A division of SANYO North America Corporation Cornerstone Business Park 1062 Thorndale Avenue Bensenville, IL 60106, U.S.A. XHX1852 XHX2452 XHX3652 UHX1852 UHX2452 UHX3652 DHX3652 DHX4852 THX1852...
  • Page 2: Important

    Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your fingers. W-3WAY_ECO-i_US.indd 2 W-3WAY_ECO-i_US.indd 2 When Installing…...
  • Page 3: Check Of Density Limit

    If a single unit of the multi air conditioner system is to be installed in a small room, select a suitable model and installation pro- cedure so that if the refrigerant accidentally leaks out,...
  • Page 4: Precautions For Installation Using New Refrigerant

    Precautions for Installation Using New Refrigerant 1. Care regarding tubing 1-1. Process tubing ● Material: Use C1220 phosphorous deoxidized copper specified in JIS H3300 “Copper and Copper Alloy Seamless Pipes and Tubes.” For tubes of ø7/8" (ø22.22 mm) or larger, use C1220 T-1/2H material or H material, and do not bend the tubes. ●...
  • Page 5: New Refrigerant R410A Cannot Be Used For Earlier Models

    3-2. Use R410A exclusive cylinder only. New refrigerant R410A cannot be used for earlier models 1. Compressor specifications are different. If recharging a R22 or R407C compressor with R410A, durability will significantly decrease since some of the materials used for compressor parts are different. 2.
  • Page 6: Table Of Contents

    IMPORTANT! ......2 Please Read Before Starting Check of Density Limit Precautions for Installation Using New Refrigerant New refrigerant R410A cannot be used for earlier models 1.
  • Page 7 5. ELECTRICAL WIRING ....68 5-1. General Precautions on Wiring 5-2. Recommended Wire Length and Wire Diameter for Power Supply System 5-3. Wiring System Diagram 5-4.
  • Page 8: General

    1. GENERAL This booklet briefly outlines where and how to install the air conditioning system. Please read over the entire set of instructions for the outdoor unit and make sure all accessory parts listed are with the system before beginning. 1-1.
  • Page 9 Table 1-2 (4-Way Air Discharge Semi-Concealed) (X-Type) Part Name Full-scale installation diagram Drain hose Hose band Drain insulator Flare insulator Insulating tape Packing Wiring cover Screw Washer Screw Table 1-3 (1-Way Air Discharge Semi-Concealed) Part Name Full-scale installation diagram Drain hose Hose band Drain insulator Flare insulator...
  • Page 10 Table 1-5 (Concealed Duct High-Static Pressure) Part Name Washer Flare insulator Drain socket Table 1-6 (Ceiling-Mounted) Part Name Full-scale installation diagram Washer Flare insulator Insulating tape Vinyl clamp Drain hose Hose band Drain insulator Gum eyelet Table 1-7 (Wall-Mounted) Part Name Tapping screw Plastic cover Insulator...
  • Page 11: Tubing Length

    1-5. Tubing Length Select the installation location so that the length and size of refrigerant tubing are within the allowable range shown in the figure below. Balance tubing (ø9.52) Explanation of symbols Distribution joint (APR: purchased separately) Ball valve (field supply) T-joint (field supply) Solidly welded shut (pinch weld)
  • Page 12 1-6. Tubing Size Table 1-10 Main Tubing Size (LA) BTU/h 95.500 153.600 Total system horsepower Combined outdoor units ø7/8" Suction tubing (ø22.22) ø3/4" Discharge tubing (ø19.05) ø3/8" ø1/2" Liquid tubing (ø9.52) (ø12.70) *1: If future extension is planned, select the tubing diameter based on the total horsepower after extension. However extension is not possible if the resulting tubing size is two ranks higher.
  • Page 13: Tubing Size

    Table 1-13 Indoor Unit Tubing Connection Size ( Indoor unit type Total system horsepower Distribution Suction tubing joint – Discharge tubing solenoid valve kit tubing Liquid tubing Solenoid valve Gas tubing kit – Indoor unit tubing connection Liquid tubing *1: For the solenoid valve kits, use type 160 with parallel specifications. Branch the tubing before and after the solenoid valve kits. 1-7.
  • Page 14: System Limitations

    Table 1-17 Refrigerant Charge Amount at Shipment (for outdoor unit) CHDZ09053 CHDZ14053 CHDZR09053 CHDZR14053 (oz) 1-9. System Limitations Table 1-18 System Limitations Max. No. allowable connected outdoor units Max. capacity allowable connected outdoor units Max. connectable indoor units Max. allowable indoor/outdoor capacity ratio *1: In the case of 20 hp (type 191.100 BTU/h) or smaller units, the number is limited by the total capacity of the connected indoor units.
  • Page 15: Check Of Limit Density

    1-11. Check of Limit Density When installing an air conditioner in a room, it is necessary to ensure that even if the refrigerant gas accidentally leaks out, its density does not exceed the limit level for that room.
  • Page 16 1-13. Optional Distribution Joint Kits See the installation instructions packaged with the distribution joint kit for the installation procedure. Table 1-19 Model name Cooling capacity after distribution 1. APR-CHRZP900BAB 2. APR-RZP224BAB 3. APR-RZP680BAB 4. APR-RZP1350BAB ■ Tubing size (with thermal insulation) 1.
  • Page 17 Table 1-21 Dimensions for connections of each part Position Dimension ø1-1/2" ø1-1/4" ø1-1/8" 2. APR-RZP224BAB Use: For indoor unit (Capacity after distribution joint is 76.400 BTU/h or less.) Example: (F below indicates inner diameter. Suction tubing 8–17/64 2–11/64 5–45/64 Thermal insulation 3.
  • Page 18: Optional Solenoid Valve Kit

    1-14. Optional Solenoid Valve Kit Precautions on Installation of Solenoid Valve Kit (1) Clean base metals thoroughly. (2) Use proper ventilation to carry fumes away from the work area. (3) Use a high quality silver based solder of at least 15 % silver. (4) Heat the base materials broadly and uniformly.
  • Page 19 ATK-RZP160BAWB Types and specifications of Part tubing connections Number Gas tube: ID5/8" Liquid tube : ID3/8" Suspension hook Liquid tube : ID3/8" Suction tube: ID5/8" Discharge tube: ID1/2" Service panel Base of control box Terminal for power line Terminal for communication line Earth (M5 with washer) Cover of control box Relay kit...
  • Page 20 Installation of Solenoid Valve Kit 1. Install the relay kit into the indoor unit. Refer to the Installation Manual for the solenoid valve kit. 2. Connect the solenoid valve kit and the relay kit in the field. Relay kit NOTE Notes on Installation •...
  • Page 21: Example Of Tubing Size Selection And Refrigerant Charge Amount

    1-15. Example of Tubing Size Selection and Refrigerant Charge Amount Additional refrigerant charging Based on the values in Tables 1-10, 11, 12, 15 and 16-2 use the liquid tubing size and length, and calculate the amount of additional refrigerant charge using the formula below. Necessary Amount of Refrigerant Charge Per Unit + 3.93 ×...
  • Page 22 2455 ft. (floor area 279 ft. ) for refrigerant of 418 oz. <Determination by calculation> Overall refrigerant charge amount for the air conditioner: oz (Minimum room volume for indoor unit: ft. 418 (oz) = 0.29 (oz/ft.
  • Page 23: Selecting The Installation Site

    2. SELECTING THE INSTALLATION SITE 2-1. Indoor Unit AVOID: ● areas where leakage of flammable gas may be expected. ● places where large amounts of oil mist exist. ● direct sunlight. ● locations near heat sources which may affect the performance of the unit.
  • Page 24: Outdoor Unit

    2-2. Outdoor Unit AVOID: ● heat sources, exhaust fans, etc. ● damp, humid or uneven locations ● indoors (no-ventilation location) ● choose a place as cool as possible. ● choose a place that is well ventilated. ● allow enough room around the unit for air intake/ exhaust and possible maintenance.
  • Page 25: Precautions When Installing In Heavy Snow Areas

    2-3. Precautions When Installing in Heavy Snow Areas a) The platform should be higher than the maximum snow depth. (Fig. 2-8) b) The 2 anchoring feet of the outdoor unit should be used for the platform, and the platform should be installed beneath the air-intake side of the outdoor unit.
  • Page 26: Dimensions Of Wind Ducting

    2-4. Dimensions of Wind Ducting Reference diagram for air-discharge chamber (field supply) Ceiling panel 33-3/16 Air direction: Front direction 35-3/64 (Ceiling panel dimensions) 35-15/64 2-11/64 (Maximum bracket dimensions) Front view Note: Can be installed so that the air direction is to the front, right, left or rear direction. 2-unit installation 74-7/32 (2-unit installation: maximum dimensions) 33-3/16...
  • Page 27: Dimensions Of Snow Ducting

    2-5. Dimensions of Snow Ducting Reference diagram for snow-proof ducting (field supply) 31-17/32 (Air intake duct) 33-3/16 (Air outlet duct) 9-13/32 35-3/64 9-13/32 (Ceiling panel dimensions) 53-55/64 1 pc. 4 pc. Front view Note: Can be installed so that the air direction is to the front, right, left or rear direction. 74-1/64 (Ceiling panel dimensions) 2-unit installation 35-3/64...
  • Page 28: How To Install The Indoor Unit

    3. HOW TO INSTALL THE INDOOR UNIT ■ 4-Way Air Discharge Semi-Concealed Type (X Type) 3-1. Preparation for Suspending This unit uses a drain pump. Use a carpenter’s level to check that the unit is level. 3-2. Suspending the Indoor Unit (1) Fix the suspension bolts securely in the ceiling using the method shown in the diagrams (Figs.
  • Page 29: Installing The Drain Piping

    (2) The length of suspension bolts must be appropriate for a distance between the bottom of the bolt and the bottom of the unit of more than 19/32 in. as shown in Fig. 3-5. (3) Thread the 3 hexagonal nuts and 2 washers (field supply) onto each of the 4 suspension bolts as shown in Fig.
  • Page 30: Checking The Drainage

    CAUTION ● In cases where it is necessary to raise the height of the drain piping, the drain piping can be raised to a maximum height of 33-15/32" above the bottom surface of the ceiling. Under no conditions attempt to raise it higher than 33-15/32"...
  • Page 31: How To Install The Ceiling Panel

    3-6. How to Install the Ceiling Panel 3-6-1. Before Installing the Ceiling Panel Checking the unit position (1) Check that the ceiling hole is within this range: 33-55/64 × 33-55/64 to 35-53/64 × 35-53/64 in. (2) Use the full-scale installation diagram (from the packaging) that was supplied with the unit to determine the positioning of the unit on the ceiling surface.
  • Page 32 3-6-2. Installing the Ceiling Panel After completing the wiring process, install the supplied wiring cover before installing the panel. It is not possible to install the wiring cover after install- ing the panel. The power must be turned ON in order to change the flap angle.
  • Page 33 3-6-3. Wiring the Ceiling Panel (1) Open the cover of the electrical component box. (2) Connect the 7P wiring connector (red) from the ceiling panel to the connector in the unit electrical component box. (Fig. 3-24) ● If the connectors are not connected, the Auto flap will not operate.
  • Page 34: Special Remarks

    Never attempt to move the louver by hand. ● Proper air flow depends on the location of the air conditioner, the layout of the room and furniture, etc. If cooling or heating seems inadequate, try changing the direction of the air flow.
  • Page 35: Preparation For Suspending

    ■ 4-Way Air Discharge Semi-Concealed Type (XM Type) 3-8. Preparation for Suspending This unit uses a drain pump. Use a carpenter’s level to check that the unit is level. 3-9. Suspending the Indoor Unit (1) Fix the suspension bolts securely in the ceiling using the method shown in the diagrams, by attaching them to the ceiling support structure, or by any other method that ensures that the unit will be securely...
  • Page 36: Installing The Drain Piping

    3-11. Installing the Drain Piping (1) Prepare standard hard PVC pipe (O.D. 1-1/32") for the drain and use the supplied hose band to prevent water leaks. (Fig. 3-33) The PVC pipe must be purchased separately. The transparent drain part on the unit allows you to check drainage.
  • Page 37: Checking The Drainage

    3-12. Checking the Drainage After wiring and drain piping are completed, use the following pro- cedure to check that the water will drain smoothly. For this, pre- pare a bucket and wiping cloth to catch and wipe up spilled water. (1) Connect power to the power terminal board (R, S terminals) inside the electrical component box.
  • Page 38 3-13-2. Installing the Ceiling Panel The power must be turned ON in order to change the flap angle. (Do not attempt to move the flap by hand. Doing so may damage the flap.) (1) Hang the temporary latches on the inside of the ceil- ing panel to the receptacle on the unit to temporarily attach the ceiling panel in place.
  • Page 39 ● Never attempt to move the louver by hand. ● Proper air flow depends on the location of the air conditioner, the layout of the room and furniture, etc. If cooling or heating seems inadequate, try changing the direction of the air flow.
  • Page 40: 1-Way Air Discharge Semi-Concealed Type (A Type)

    ■ 1-Way Air Discharge Semi-Concealed Type (A Type) 3-14. Suspending the Indoor Unit (1) Follow the diagrams to make the holes in the ceiling. (Figs. 3-52 and 3-53) (2) Depending on the ceiling type: ● Insert suspension bolts as shown in Fig. 3-54 ●...
  • Page 41: Suspending The Indoor Unit

    3-15. Placing the Unit Inside the Ceiling Be sure to use a level gauge CAUTION and confirm that the unit is level. If it is not level, water leakage may occur. (1) Use the supplied M5 or 3/16" screws (4) to attach the full-size installation diagram to the indoor unit suspension lugs, in order to obtain the ceiling opening dimensions for suspending the unit.
  • Page 42: Installing The Drain Piping

    CAUTION ● The indoor unit includes a drain pump. Be sure to use a level gauge and verify that the unit is level. ● Before inserting the ceiling material, complete as much of the drain piping work and refrigerant tubing work as possible. (6) The distance between the unit and the opening of the ceiling and the distance between the bottom surface of the ceiling and the bottom surface of the...
  • Page 43: Checking The Drainage

    CAUTION ● Do not install an air bleeder as this may cause water to spray from the drain pipe outlet. (Fig. 3-64) ● In cases where it is necessary to raise the height of the drain piping, the drain piping can be raised to a maximum height of 33-15/32"...
  • Page 44: Electrical Power Wiring

    3-18. Electrical Power Wiring (1) Wiring connections The power inlet is on the side of the indoor unit where the refrigerant tubing is located. The electrical component box is on the lower air intake surface of the indoor unit. (Fig. 3-69) (2) Wiring WARNING ●...
  • Page 45 Removing the intake grille Slide the intake grille hooks (2 locations) in the direction of the arrow to open the intake grille. (Fig. 3-72) When the intake grille is open, press a flathead screwdriver against the rear tabs (2 locations) and pull out the intake grille.
  • Page 46 (5) Align the installation holes on the panel with the bolt holes on the unit. (6) Insert the supplied washer head bolts into the 4 panel installation holes, and tighten until the panel is securely fastened against the unit. (Fig. 3-77) (7) Verify that the panel is securely fastened against the unit.
  • Page 47 3-19-3. Wiring the ceiling panel (1) Loosen the 2 screws on the electrical component box lid, and remove the lid. (Fig. 3-80) (2) Fasten the wiring connector (7P, red) which comes out from the ceiling panel using the lead wire clamps (2 locations) on the unit.
  • Page 48: Concealed Duct Type (U Type)

    3-20. Required Minimum Space for Installation and Service ● This air conditioner is usually installed above the ceiling so that the indoor unit and ducts are not visible. Only the air intake and air outlet ports are visible from below.
  • Page 49: Suspending The Indoor Unit

    3-21. Suspending the Indoor Unit Depending on the ceiling type: • Insert suspension bolts as shown in Fig. 3-86 • Use existing ceiling supports or construct a suitable support as shown in Fig. 3-87. It is important that you use extreme care WARNING in supporting the indoor unit inside the ceiling.
  • Page 50: Installing The Drain Piping

    3-22. Installing the Drain Piping (1) Prepare standard hard PVC pipe (O.D. 1-1/4") for the drain and use the supplied hose band to prevent water leaks. The PVC pipe must be purchased separately. The transparent drain part on the unit allows you to check drainage.
  • Page 51: Increasing The Fan Speed

    Be careful since the fan will start when you CAUTION short the pin on the indoor control board. (4) When the check of drainage is complete, open the check pin (CHK) and remount the insulator and drain cap onto the drain inspection port. 3-24.
  • Page 52: Concealed Duct High-Static Pressure Type (D Type)

    3-25. Required Minimum Space for Installation and Service ● This air conditioner is usually installed above the ceiling so that the indoor unit and ducts are not visible. Only the air intake and air outlet ports are visible from below.
  • Page 53: Suspending The Indoor Unit

    3-26. Suspending the Indoor Unit Depending on the ceiling type: ● Insert suspension bolts as shown in Fig. 3-102 ● Use existing ceiling supports or construct a suitable support as shown in Fig. 3-103. It is important that you use extreme care WARNING in supporting the indoor unit inside the ceiling.
  • Page 54: Installing The Drain Piping

    / air flow noise increases. ● If the air conditioner is to be installed in a room such as an office or meeting room which needs a low sound level, provide a supply and return noise absorption chamber with an acoustic liner.
  • Page 55: Ceiling-Mounted Type (T Type)

    ■ Ceiling-Mounted Type (T Type) 3-30. Required Minimum Space for Installation and Service (1) Dimensions of suspension bolt pitch and unit Table 3-6 Unit: in. Dimension Type 12, 18 33-21/32 35-53/64 8-17/64 44-19/64 46-29/64 8-17/64 (2) Refrigerant tubing • drain hose position Left side 9-7/8 Closed with rubber stopper at time of shipment.
  • Page 56: Suspending The Indoor Unit

    (4) Wall and ceiling side opening position Figure shows view from front ø3-15/16 wall side opening 3-35/64 ø3-15/16 wall side opening (for left-side drain hose) * If the optional drain up kit is installed, create a ø3-15/16" hole along the dotted line (part marked with * in figure). 3-31.
  • Page 57 (5) Before suspending the indoor unit, remove the 2 or 3 screws on the latch of the air-intake grilles, open the grilles, and remove them by pushing the claws of the hinges as shown in Fig. 3-117. Then remove both side panels sliding them along the unit toward the front after removing the 2 attachment screws.
  • Page 58: Duct For Fresh Air

    3-32. Duct for Fresh Air There is a duct connection port (knock-out hole) at the right- rear of the top panel of the indoor unit for drawing in fresh air. If it is necessary to draw in fresh air, remove the cover by opening the hole and connecting the duct to the indoor unit through the connection port.
  • Page 59 ● Never allow traps to occur in the course of the piping. ● Insulate any piping inside the room to prevent drip- ping. ● After the drain piping, pour water into the drain pan to check that the water drains smoothly. ●...
  • Page 60: Wall-Mounted Type (K Type)

    ■ Wall-Mounted Type (K Type) 3-35. Removing the Rear Panel from the Unit (1) Remove the set screws used to fasten the rear panel to the indoor unit during transportation. (2) Press up on the frame at the 2 locations shown by the arrows in the figure at right, and remove the rear panel.
  • Page 61: Removing The Grille To Install The Indoor Unit

    (2) Check with a tape measure or carpenter’s level. This is important so that the unit is correctly installed. (Fig. 3-140) (3) Make sure the panel is flush against the wall. Any space between the wall and unit will cause noise and vibration. b) If the Wall is Brick, Concrete or Similar Drill 3/16"...
  • Page 62: Shaping The Tubing

    (3) To mount the indoor unit on the rear panel. 1. When installing the indoor unit, position the indoor unit onto the installation tabs on the upper part of the rear panel. (Fig. 3-146) 2. Press on the air outlet to hold it in place, and press the lower part of the indoor unit until a “click”...
  • Page 63: When Using Wireless Remote Controller Instead Of Wired Remote Controller

    3-42. When Using Wireless Remote Controller Instead of Wired Remote Controller When the wireless remote controller is to be used, slide the switch on the indoor unit control PCB. • If this setting is not made, an alarm will occur. (The operation lamp on the display blinks.) •...
  • Page 64: How To Install The Outdoor Unit

    4. HOW TO INSTALL THE OUTDOOR UNIT 4-1. Transporting When transporting the unit, have it delivered as close to the installation site as possible without unpacking. Use a hook for suspending the unit. (Fig. 4-1) CAUTION ● When hoisting the outdoor unit, pass ropes or straps under the bottom plate as shown in the figure at right.
  • Page 65: Remove The Brackets Used For Transport

    4-3. Remove the Brackets Used for Transport ● After installing the unit, remove the 2 transport brackets from the front and rear (4 brackets total). (Fig. 4-5) 4-4. Routing the Tubing ● The tubing can be routed out either from the front or from the bottom. (Fig. 4-6) ●...
  • Page 66: Prepare The Tubing

    4-5. Prepare the Tubing ● Material: Use C1220 phosphorous deoxidized copper as described in JIS H3300, “Copper and Copper Alloy Seamless Pipes and Tubes.” (For tubes that are ø1" (ø25.4 mm) or larger, use 1/2H material or H material. For all others use O material.) ●...
  • Page 67 ● Tighten each cap as specified below. Tightening torque for each cap Service port cap 60 – 100 lbs · in (70 – 120 kgf · cm) (width 19/32") Valve cap 170 – 220 lbs · in (200 – 250 kgf · cm) (width 55/64") Flare nut 300 –...
  • Page 68: Electrical Wiring

    For field wiring rules, please refer to your LOCAL ELECTRICAL CODES before beginning. You must ensure that installation complies with all relevant rules and regulations. (8) To prevent malfunction of the air conditioner caused by electrical noise, care must be taken when wiring as follows: ●...
  • Page 69: Wiring System Diagram

    5-3. Wiring System Diagram ● For K, A, X, T, U and D Types Power supply 208 / 230V, 1ø, ~60Hz Ground Remote controller Power supply 208 / 230V, 1ø, ~60Hz Ground Remote controller Group control: Power supply 208 / 230V, 1ø, ~60Hz Ground Power supply 208 / 230V, 1ø, ~60Hz...
  • Page 70 ● For XM Type Indoor unit (No. 1) Power supply 208/230V, 1ø, ~60Hz Ground Remote controller Indoor unit (No. 2) Power supply 208/230V, 1ø, ~60Hz Ground Remote controller Indoor unit Group control: (No. 3) Power supply 208/230V, 1ø, ~60Hz Ground Indoor unit (No.
  • Page 71 CAUTION (1) When linking outdoor units in a network (S-net link system), disconnect the terminal extended from the short plug (CN003, 2P Black, location: right bottom on the outdoor main control PCB) from all outdoor units except any one of the outdoor units.
  • Page 72 Loose wiring may cause the terminal to overheat or result WARNING in unit malfunction. A fire hazard may also exist. Therefore, ensure that all wir- ing is tightly connected. When connecting each power wire to the terminal, fol- low the instructions on “How to connect wiring to the terminal”...
  • Page 73: Important Note When Wiring For Common Type

    5-4. Important Note When Wiring for Common Type Connect the wires referring to the diagram. Note that the remote control wires and the power supply wires are not supplied. The remote control wires shall be segregated from the power supply wires as follows: Install the optional remote control wires (field supplied) and the manufacturer supplied 3-way wiring harness to the electrical connection box as shown in the diagram.
  • Page 74 Important Note When Wiring for Common Type (Continued) D Type Optional remote control wire (field supplied) Power wiring Earth screw (field supplied) K Type Model : KHX0752/0952/1252/1852 Clamping strap Power wiring (field supplied) Conduit W-3WAY_ECO-i_US.indd 74 W-3WAY_ECO-i_US.indd 74 T Type Clamping clip Clamping...
  • Page 75: Important Note When Wiring For Xm Type

    5-5. Important Note When Wiring for XM Type Connect the wires referring to the diagram. Note that the remote control wires and the power supply wires are not supplied. The remote control wires shall be segregated from the power supply wires as follows: Install the optional remote control wires (field supplied) and the manufacturer supplied 3-way wiring harness to the electrical connection box as shown in the diagram.
  • Page 76: How To Process Tubing

    6. HOW TO PROCESS TUBING The liquid tubing side is connected by a flare nut, and the gas tubing side is connected by brazing. 6-1. Connecting the Refrigerant Tubing Use of the Flaring Method Many of conventional split system air conditioners employ the flaring method to connect refrigerant tubes which run between indoor and outdoor units.
  • Page 77: Connecting Tubing Between Indoor And Outdoor Units

    Caution Before Connecting Tubes Tightly (1) Apply a sealing cap or water-proof tape to prevent dust or water from entering the tubes before they are used. (2) Be sure to apply refrigerant lubricant to the match- ing surfaces of the flare and union before connecting them together.
  • Page 78: Insulating The Refrigerant Tubing

    6-3. Insulating the Refrigerant Tubing Tubing Insulation ● Thermal insulation must be applied to all unit tubing, including the distribution joint (purchased separately). (Fig. 6-7) * For gas tubing, the insulation material must be heat resistant to 248°F or above. For other tubing, it must be heat resistant to 176°F or above.
  • Page 79: Taping The Tubes

    6-4. Taping the Tubes (1) At this time, the refrigerant tubes (and electrical wir- ing if local codes permit) should be taped together with armoring tape in 1 bundle. To prevent the con- densation from overflowing the drain pan, keep the drain hose separate from the refrigerant tubing.
  • Page 80: Air Purging With A Vacuum Pump (For Test Run) Preparation

    7. AIR PURGING Air and moisture in the refrigerant system may have undesirable effects as indicated below. ● pressure in the system rises ● operating current rises ● cooling (or heating) efficiency drops ● moisture in the refrigerant circuit may freeze and block capillary tubing ●...
  • Page 81 (3) Do a leak test of all joints of the tubing (both indoor and outdoor) and all service valves. Bubbles indicate a leak. Wipe off the soap with a clean cloth after a leak test. (4) After the system is found to be free of leaks, relieve the nitrogen pressure by loosening the charge hose connector at the nitrogen cylinder.
  • Page 82 NOTE The required time in the above table is calculated based on the assumption that the ideal (or target) vacuum condition is less than –14.7 psig (–755 mm Hg, 5 Torr). (2) When the desired vacuum is reached, close the “Lo” knob of the manifold valve and turn off the vacuum pump.
  • Page 83: Preparing For Test Run

    8. TEST RUN 8-1. Preparing for Test Run ● Before attempting to start the air conditioner, check the following. (1) The control wiring is correctly connected and all electrical connections are tight. (2) The transportation pads for the indoor fan have been removed.
  • Page 84: Test Run Procedure

    8-2. Test Run Procedure Recheck the items to check before the test run. Have the outdoor sub units been connected? <Outdoor unit control PCB> Unit No. setting switch Set the unit address. (S007) <Outdoor unit control PCB> Unit No. setting switch Set the No.
  • Page 85 Examples of the No. of indoor units settings (S005, S004) Indoor unit setting (S005) No. of indoor units 1 unit (factory setting) All OFF 11 units 21 units 31 units 40 units 1 & 3 ON Examples of refrigerant circuit (R.C.) address settings (required when link wiring is used) (S003, S002) System address No.
  • Page 86: Main Outdoor Unit Pcb Setting

    8-3. Main Outdoor Unit PCB Setting W-3WAY_ECO-i_US.indd 86 W-3WAY_ECO-i_US.indd 86 S007 S006 S005 S004 S002 S003 Fig. 8-4 CN003 CN101 CN100 2008/02/07 10:56:12 2008/02/07 10:56:12...
  • Page 87: Auto Address Setting

    8-4. Auto Address Setting Basic wiring diagram: Example (1) • If link wiring is not used (The inter-unit control wires are not connected to multiple refrigerant systems.) Indoor unit addresses can be set without operating the compressors. No. 1 (main unit) settings System address (system 1 setting)
  • Page 88 Basic wiring diagram: Example (2) No. 1 (main unit) settings System address (system 1 setting) (S002) (S003) No. of Unit (S006) outdoor units number (2 units setting setting) (unit No. 1) Outdoor unit system 1 Indoor unit Remote controller System address (system 2 setting) (S002) (S003)
  • Page 89 Case 1 Automatic Address Setting (no compressor operation) ● Indoor and outdoor unit power can be turned ON for each system separately. Indoor unit addresses can be set without operating the compressors. Automatic Address Setting from Outdoor Unit 1. On the outdoor main unit control PCB, check that the system address rotary switch (S002) is set to “1” and that the DIP switch (S003) is set to “0”...
  • Page 90 Case 2 Automatic Address Setting in Heating Mode ● Indoor and outdoor unit power cannot be turned ON for each system separately. In the following, automatic setting of indoor unit addresses is not possible if the compressors are not operating. Therefore perform this process only after completing all refrigerant tubing work.
  • Page 91 Case 3 Automatic Address Setting in Cooling Mode ● Indoor and outdoor unit power cannot be turned ON for each system separately. In the following, automatic setting of indoor unit addresses is not possible if the compressors are not operating. Therefore perform this process only after completing all refrigerant tubing work.
  • Page 92 Display during automatic address setting ● On outdoor main unit PCB * Do not short-circuit the automatic address setting pin (CN100) again while automatic address set- ting is in progress. Doing so will cancel the setting operation and will cause LEDs 1 and 2 to turn OFF.
  • Page 93: Remote Controller Test Run Settings

    Request concerning recording the indoor/outdoor unit combination Nos. After automatic address setting has been completed, be sure to record them for future reference. List the outdoor main unit system address and the addresses of the indoor units in that system in an easily visible loca- tion (next to the nameplate), using a permanent marking pen or similar means that cannot be abraded easily.
  • Page 94: Meaning Of Alarm Messages

    8-7. Meaning of Alarm Messages Table of Self-Diagnostics Functions and Description of Alarm Displays Alarm messages are indicated by the blinking of LED 1 and 2 (D72, D75) on the outdoor unit PCB. They are also displayed on the wired remote controller. ●...
  • Page 95 Possible cause of malfunction Activation of Protective device in indoor unit protective is activated. device Protective device in outdoor unit is activated. Indoor thermistor is either open Thermistor or damaged. fault Outdoor thermistor is either open or damaged. EEP ROM on indoor unit P.C.B. failure Protective device for compressor Protective No.
  • Page 96 Alarm messages displayed on system controller Serial Error in transmitting serial communication communication signal errors Mis-setting Error in receiving serial communication signal Protective device of sub indoor Activation of protective unit in group control is activated. device NOTE 1. Alarm messages in << >> do not affect other indoor unit operations. 2.
  • Page 97: Appendix

    X type (4-WAY) ■ CARE AND CLEANING 1. For safety, be sure to turn the air conditioner off and also to disconnect the power before WARNING cleaning. 2. Do not pour water on the indoor unit to clean it. This will damage the internal components and cause an electric shock hazard.
  • Page 98 Care: Before a prolonged idle period ■ TROUBLESHOOTING If your air conditioner does not work properly, first check the following points before requesting service. If it still does not work prop- erly, contact your dealer or a service center. Trouble Air conditioner does not r un at all 1.
  • Page 99: 1-Way Air Discharge Semi-Concealed Type

    SEMI-CONCEALED A type (1-WAY) ■ CARE AND CLEANING 1. For safety, be sure to turn the air conditioner off and also to disconnect the power WARNING before cleaning. 2. Do not pour water on the indoor unit to clean it. This will damage the internal compo- nents and cause an electric shock hazard.
  • Page 100 Care: After a prolonged idle period Care: Before a prolonged idle period ■ TROUBLESHOOTING If your air conditioner does not work properly, first check the following points before requesting service. If it still does not work properly, contact your dealer or a service center. Trouble Air conditioner does not r un at all 1.
  • Page 101: Concealed Duct (High-Static Pressure) Type (U, D Types)

    *Concealed duct type (U, D): Type Period An air filter is not provided with this air conditioner at the time of shipment. To get clean air (Depends on filter U, D* and to extend the service life of the air conditioner, an air filter must be installed in the air specifications) intake.
  • Page 102: Troubleshooting

    ■ TROUBLESHOOTING If your air conditioner does not work properly, first check the following points before requesting service. If it still does not work properly, contact your dealer or a service center. Trouble Air conditioner does not r un at all 1.
  • Page 103: Ceiling-Mounted Type (T Type)

    9-4. Ceiling-Mounted Type (T Type) ■ NAME OF PARTS ■ CARE AND CLEANING 1. For safety, be sure to turn the air conditioner off and also to disconnect the power before WARNING cleaning. 2. Do not pour water on the indoor unit to clean it. This will damage the internal components and cause an electric shock hazard.
  • Page 104 Care: After a prolonged idle period Care: Before a prolonged idle period ■ TROUBLESHOOTING If your air conditioner does not work properly, first check the following points before requesting service. If it still does not work properly, contact your dealer or a service center. Trouble Air conditioner does not r un at all 1.
  • Page 105: Wall-Mounted Type (K Type)

    K Type (Wall-Mounted) ■ CARE AND CLEANING 1. For safety, be sure to turn the air conditioner off and also to disconnect the power before WARNING cleaning. 2. Do not pour water on the indoor unit to clean it. This will damage the internal components and cause an electric shock hazard.
  • Page 106 Care: Before a prolonged idle period ■ TROUBLESHOOTING If your air conditioner does not work properly, first check the following points before requesting service. If it still does not work properly, contact your dealer or a service center. Trouble Air conditioner does not r un at all 1.

Table of Contents