Samson SAM -01 Mounting And Operating Instructions page 25

Linear actuator type sam -01 to sam -52
Table of Contents

Advertisement

       
- Type SAM-01 to SAM-11 Linear Actuators -
The travel limit switches WE-S3 and WE-S6
are mounted on the lateral mounting plate.
They are operated via the operating cams lo-
cated at the top end of the actuator stem.
Depending on the movement of the actuator
stem "OPEN"/"CLOSED", the associated
limit switch deactivates the actuator travel.
You can adjust the switching position at ran-
dom by moving the respective switch axially
over the oblong hole, retighten.
S3
S6
Fig. 20 ⋅ Operating cams WE-S3/WE-S6
WE-S3
– Move actuator stem to final position ma-
nually ("OPEN") - actuator stem retracted -.
First, the switch WE-S3 must be above from
the operating cam.
WE-S6
– Move actuator stem to final position ma-
nually ("CLOSED")
tracted -.
First, the switch WE-S6 must be below the
operating cam.
For both cases ...
– Loosen the mounting screws of the respec-
tive switch from the back side so that the
"OPEN"
switch may be operated.
– Push the switch up/down until the operating
cams switch off the actuator - depending on
the travel - (check with a gauge).
Actuator stem
– Retighten mounting screws.
Check switching position in a test run.
"CLOSED"
&+ #  &, 
- actuator stem re-