™ FieldPoint Operating Instructions FP-AI-110 and cFP-AI-110 Eight-Channel, 16-Bit Analog Input Modules These operating instructions describe how to install and use the FP-AI-110 and cFP-AI-110 analog input modules (referred to inclusively as the [c]FP-AI-110). For information about configuring and accessing the [c]FP-AI-110 over a network, refer to the user manual for the FieldPoint network module you are using.
Page 3
To install the FP-AI-110, refer to Figure 1 and complete the following steps: 1. Slide the terminal base key to either position X (used for any module) or position 1 (used for the FP-AI-110). 2. Align the FP-AI-110 alignment slots with the guide rails on the terminal base.
Page 5
is 2 A or less and the maximum current through any V terminal is 1 A or less. Install a 2 A maximum, fast-acting fuse between the external power supply and the V terminal on each channel. The wiring diagrams in this document show fuses where appropriate. Table 1 lists the terminal assignments for the signals associated with each channel.
Page 7
Figure 5 shows how to connect a voltage source with an external power supply to one channel of the [c]FP-AI-110. 10–30 VDC External Power Supply – (Optional) To Analog Powered Input Circuitry Voltage Transducer – To Next Channel [c]FP-AI-110 Figure 5. Voltage Source with External Power Supply Measuring Current with the [c]FP-AI-110 The input ranges for current sources are 0–20, 4–20, and ±20 mA.
Page 9
Overranging The [c]FP-AI-110 has an overranging feature that measures a little beyond the nominal values of each range. For example, the actual measurement limit of the ±10 V range is ±10.4 V. The overranging feature enables the [c]FP-AI-110 to compensate for field devices with span errors of up to +4% of full scale.
Page 11
working voltages of 250 V . Safety standards (such as those published by UL and IEC) require the use of double insulation between hazardous voltages and any human-accessible parts or circuits. Never try to use any isolation product between human-accessible parts (such as DIN rails or monitoring stations) and circuits that can be at hazardous potentials under normal conditions, unless the product is specifically designed for such an application, as is the...
Safety Guidelines for Hazardous Voltages If hazardous voltages are connected to the module, take the following precautions. A hazardous voltage is a voltage greater than 42.4 V or 60 VDC to earth ground. peak Ensure that hazardous voltage wiring is Caution performed only by qualified personnel adhering to local electrical standards.
Page 15
Input current 25 °C........... 400 pA typ, 1 nA max 70 °C........... 3 nA typ, 15 nA max Input noise (with 50 or 60 Hz filter enabled) ±60 mV range......±3 LSB peak-to-peak ±300 mV range......±2 LSB peak-to-peak Other ranges ....... ±1 LSB peak-to-peak Typical and warranted accuracy by input range and temperature range Typical Accuracy...
Page 17
Physical Characteristics Indicators .......... Green POWER and READY indicators Weight FP-AI-110........140 g (4.8 oz) cFP-AI-110......... 110 g (3.7 oz) Power Requirements Power from network module .... 350 mW Safety Isolation Voltage Channel-to-ground isolation Continuous ......... 250 V , Measurement Category II Dielectric withstand....
Page 19
CE Compliance This product meets the essential requirements of applicable European Directives, as amended for CE marking, as follows: Low-Voltage Directive (safety)..73/23/EEC Electromagnetic Compatibility Directive (EMC) ....... 89/336/EEC Refer to the Declaration of Conformity (DoC) for Note this product for any additional regulatory compliance information.
National Instruments corporate headquarters is located at 11500 North Mopac Expressway, Austin, Texas, 78759-3504. National Instruments also has offices located around the world to help address your support needs. For telephone support in the United...
Page 21
National Instruments, NI, ni.com, and LabVIEW are trademarks of National Instruments Corporation. Refer to the Terms of Use section on ni.com/legal for more information about National Instruments trademarks. Other product and company names mentioned herein are trademarks or trade names of their respective companies.