DMC-GRMS-UL
Guest Room Modular
Controller
Devices must be installed by a
qualified electrician in accordance with
all national and local electrical and
construction codes and regulations.
Les appareils doivent être installés par un
électricien diplômé conformément à tous les
codes et réglementations électriques et de
construction nationaux et locaux.
Die Geräte sind von einem qualifizierten Elektriker
in Übereinstimmung mit allen geltenden
Vorschriften zu installieren.
1
IEC Pollution Degree II
Los dispositivos deben ser instalados por un
electricista calificado y cumpliendo todas las
normas y regulaciones, tanto nacionales como
locales, sobre instalaciones eléctricas y obras.
I dispositivi devono essere installati da un
elettricista qualificato in conformità con le norme
locali e nazionali vigenti in materia di costruzioni
edilizie e installazione di impianti elettrici.
De apparaten moeten worden aangebracht
door een gekwalificeerde elektricien en in
overeenstemming met alle nationale en
plaatselijke elektriciteits- en bouwvoorschriften.
X 4
X 4
RJ45 X 3
Installation Instructions
Instructions d'installation
Installationsanweisungen
Instrucciones de instalación
Istruzioni per l'installazione
Installatie-instructies
インストール手順
安装指示
装置を取り付ける際は、 資格のある電気技師に依頼し、
国および地域の電気および建設に関するすべての法令に
従ってください。
根据国家/地区及当地的电气与建筑规范和法规,该设
备必须由有资质的电工进行安装。
244 mm (9.61 in)
286 mm (11.26 in)
2
≤90%
40° C (104° F)
0° C (32° F)
.
320 mm (12.60 in)
107 mm
(4.21 in)
www.lighting.philips.com/dynalite

Advertisement

loading

Summary of Contents for Philips Dynalite DMC-GRMS-UL

  • Page 1 Vorschriften zu installieren. RJ45 X 3 244 mm (9.61 in) 320 mm (12.60 in) 107 mm (4.21 in) 286 mm (11.26 in) IEC Pollution Degree II ≤90% 40° C (104° F) www.lighting.philips.com/dynalite 0° C (32° F)
  • Page 2 Output Ratings / Channel (CH) Load Type CH9 - CH13 CH14, CH16 CH15, CH17 CH18 - CH19 OUT1 - OUT3 16 A, 277 V (N/O) General Use 16 A, 277 V 16 A, 277 V 16 A, 277 V 1 A, 30 V 4 A, 250 V (N/C) Resistive...
  • Page 3 ≤ 5 mm 100-240 V ± 10% 20 A CH1-4-L-IN 10+ AWG CH1-4-N-IN µP CH1-L-OUT CH1-N-OUT D– CH1-4-L-IN CH2-L-OUT DMX Tx CH2-N-OUT CH1-4-N-IN 0.5 Nm CH3-L-OUT 4.4 Lb-in CH3-N-OUT L/DA+ CH4-L-OUT D– 12/24 V N/DA- CH4-N-OUT 200 mA L/DA+ SHLD Port 1 N/DA- DyNet RS-485...
  • Page 4 DGCM102 DGFM102 DGRM204 DGBM200 DGTM104 1 x 2 A curtain 1 x 2 A fan 2 x 4 A relay 2 CH ballast 1 x 4 A Trailing Edge module module module module dimmer module DGLM202 DGTM202 DGLM105 DGLM402 DGTM402 2 x 2 A Leading Edge 2 x 2 A Trailing Edge 1 x 5 A Leading Edge...
  • Page 5 DGFM102 1 x 2 A fan module CH1-4-L-IN CH1-4-N-IN L/DA+ CH 1 N/DA– L/DA+ CH 2 N/DA– L/DA+ CH 3 N/DA– Load Type Output Ratings per Channel L/DA+ CH 4 N/DA– Motor x 1 400 VA, 230 V Not suitable for 120 V (Not UL listed) DGRM204 2 x 4 A...
  • Page 6 Module supply must be on same phase as controller supply DGTM104 1 x 4 A TE dimmer module CH1-4-L-IN CH1-4-N-IN L/DA+ CH 1 N/DA– L/DA+ CH 2 N/DA– Load Type Output Ratings per Channel L/DA+ CH 3 N/DA– Incandescent 4 A, 120(UL) / 230 V Electronic L/DA+ 4 A, 120(UL) / 230 V...
  • Page 7 Module supply must be on same phase as controller supply DGLM105 1 x 5 A LE dimmer module CH1-4-L-IN CH1-4-N-IN L/DA+ CH 1 N/DA– Load Type Output Ratings per Channel L/DA+ CH 2 Incandescent 5 A, 120 / 230 V N/DA–...
  • Page 8 CH14-IN CH14-OUT CH15-IN CH15A-OUT CH15B-OUT CH16-IN CH16-OUT CH17-IN CH17A-OUT CH17B-OUT CH14-IN CH14-OUT CH15-IN CH15A-OUT CH15B-OUT CH16-IN CH16-OUT CH17-IN CH17A-OUT CH17B-OUT SELV/CLASS 2 POWER/CLASS 1 SELV/CLASS 2 CLASS 2 CLASS 1 CLASS 2 CLASS 1 CLASS 2...
  • Page 9 PORT 2 FLOOR 9 16 PORT 2 FLOOR PORT 2 FLOOR PORT 1 ROOM PORT 1 ROOM DyNet RS-485 DyNet RS-485 DMX 512 DMX 512...
  • Page 10 ≤ 2.5 mm 12+ AWG 0.5 Nm 4.4 Lb-in DMX SWITCH ROOM ≤ 2.5 mm +12/24 V 12+ AWG ≤ 2 A 0.5 Nm DyNet RS-485 SHLD 4.4 Lb-in ROOM +12/24 V +12/24 V DyNet RS-485 ≤ 2.5 mm +12/24 V FLOOR 12+ AWG ≤...
  • Page 11: Dry Contact Inputs

    UL924 DRY CONTACT INPUTS < 20 m 1 2 3 4 5 6 7 8 ROOM ADDRESS DRY CONTACT OUTPUTS DyNet RS-485 ≤ 2.5 mm 0.5 Nm 4.4 Lb-in 12+ AWG ≤ 5 mm 10+ AWG 0.6 Nm 5.5 Lb-in Refer to product label for Earth bar and Neutral bar wire gauge and torque ratings...
  • Page 12 HD 384.5.523 shall not be exceeded. This Class B digital apparatus complies with Canadian ICES-003: CAN ICES-3(B)/NMB-3(B). Cet appareil numerique de la classe B est conforme a la norme NMB- 003 du Canada: CAN ICES-3(B)/NMB-3(B). Philips Dynalite www.lighting.philips.com/dynalite © 2018 Signify Holding. All rights reserved.