Penn A421 Series Installation Manual

Penn A421 Series Installation Manual

Temperature controls with off-cycle defrost
Hide thumbs Also See for A421 Series:
Table of Contents

Advertisement

Applications
Important: Use this A421 Series Electronic Temperature Control only as an operating control.
Where failure or malfunction of the A421 Control could lead to personal injury or property
damage to the controlled equipment or other property, additional precautions must be
designed into the control system. Incorporate and maintain other devices, such as supervisory
or alarm systems or safety or limit controls, intended to warn of or protect against failure or
malfunction of the A421 Control.
Important: Utiliser ce A421 Series Electronic Temperature Control uniquement en tant que
dispositif de régulation. Lorsqu'une défaillance ou un dysfonctionnement du A421 Control
risque de provoquer des blessures ou d'endommager l'équipement contrôlé ou un autre
équipement, la conception du système de contrôle doit intégrer des dispositifs de protection
supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs,
tels que des systèmes de supervision ou d'alarme, ou des dispositifs de sécurité ou de
limitation, ayant une fonction d'avertissement ou de protection en cas de défaillance ou de
dysfonctionnement du A421 Control.
The A421 Series Electronic Temperature Controls are single-stage, electronic temperature controls
with a single-pole, double-throw (SPDT) output relay.
A421 Controls feature a backlit LCD with adjustable brightness and three-button touchpad interface
that you can set up to restrict user adjustments. An LED indicates the output relay's on/off status.
A421 Controls have simple on and off temperature settings for heating or cooling, an adjustable
anti-short cycle delay, temperature setback, and sensor offset capability. The temperature control
range is -40°F to 212°F or -40°C to 100°C.
The A421 Controls are available either in Type 1 (NEMA), IP20 (CE), high-impact plastic enclosures
suitable for surface or DIN rail mounting (Figure 1), or in Type 4X (NEMA), IP66 (CE) watertight,
corrosion resistant surface mount enclosures (Figure 2).
Part No. 24-7664-3035 Rev D
2018-11-13
A421 Series Electronic Temperature
Controls with Off-Cycle Defrost Installation
Guide
A421ABD-x, A421AED-x

Advertisement

Table of Contents
loading

Summary of Contents for Penn A421 Series

  • Page 1 Guide Applications Important: Use this A421 Series Electronic Temperature Control only as an operating control. Where failure or malfunction of the A421 Control could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system.
  • Page 2 0 for no defrost interval. You can also start or stop a defrost cycle in the following two ways: use the three-button touchpad on the Advanced Menu or connect a momentary switch to the binary input (BI). A421 Series Electronic Temperature Controls with Off-Cycle Defrost Installation Guide...
  • Page 3 The A421 Controls require an A99 sensor, and each A421 Control includes an A99 sensor. Any A99 Series sensor works with the A421 Series Controls. Do not replace an A99 Series sensor with any other brand, series, or type of temperature sensor. See...
  • Page 4 LCD, to bring the electrical connection to the top or bottom of the mounted control. Note: Do not twist the wiring harness between the enclosure base and cover more than 180º. A421 Series Electronic Temperature Controls with Off-Cycle Defrost Installation Guide...
  • Page 5 Observe the wire size restrictions listed in Table 2 and the electrical ratings listed in Technical specifications. Observe the following guidelines, procedures, and illustrations when you wire an A421 Series control and A99 Series sensor. • Select the appropriate A99 sensors for the ambient operating range that the A421 Control monitors and controls, as shown in Table 6.
  • Page 6 You can also provide an independent power source for the A421 Control on the TB1 terminals and then wire the TB2 relay terminals to a separate power source to switch and power the controlled equipment circuit. A421 Series Electronic Temperature Controls with Off-Cycle Defrost Installation Guide...
  • Page 7 Figure 4: Wiring the A421 Series Controls using the same power source to power the control operation and power the controlled equipment Table 2: A421 Control wiring terminals and wire size information Terminal Label Description, function, and requirements Wire sizes block...
  • Page 8 Connects the low-voltage input signal wire from control sensors. Setup and adjustments The front panel of the A421 Series Electronic Temperature Control has an LCD and a three-button UI as shown in the following figure. Figure 5: A421 Control front panel with LCD and three-button UI The A421 Series Control has a backlit LCD screen (Figure 5).
  • Page 9 When you select your required On and OFF values, the control automatically determines the mode of operation and displays the proper mode icon on the Main screen. Note: The A421 Series Controls do not have jumpers for setting up the heating or cooling mode.
  • Page 10 The HtS and LtS values define the restricted adjustment temperature range and are enforced only when the A421 Control is set to the restricted adjustment mode (Figure 12). Restricting user adjustment. A421 Series Electronic Temperature Controls with Off-Cycle Defrost Installation Guide...
  • Page 11 Setting the dl value to 0 eliminates regular or timed defrost cycles. You can still start or stop a defrost cycle by setting the SdF parameter or by using the binary input. A421 Series Electronic Temperature Controls with Off-Cycle Defrost Installation Guide...
  • Page 12 10 = brightest backlight backlight) setting Defrost Cycle Time (Advanced only) 1 minutes to 99 minutes 30 minutes Defrost Interval (Advanced only) 0 or 2 hours to 24 hours 8 hours A421 Series Electronic Temperature Controls with Off-Cycle Defrost Installation Guide...
  • Page 13 Note: If you do not press MENU to save a new value, the control reverts to the last saved value. After 30 seconds of inactivity while in any screen, the control reverts to the Main screen. A421 Series Electronic Temperature Controls with Off-Cycle Defrost Installation Guide...
  • Page 14 With the preferred parameter value displayed, press MENU to save the displayed value and go to the next parameter code. To exit the Basic menu and go to the Advanced menu, simultaneously press and hold Down and Up, for 5 seconds. A421 Series Electronic Temperature Controls with Off-Cycle Defrost Installation Guide...
  • Page 15 • Sensor Failure Option (SO) • Start or Stop Defrost Cycle (SdF) Parameter codes and modes of operation and Table 3 for more information about parameter codes, usable parameter values, and default values. A421 Series Electronic Temperature Controls with Off-Cycle Defrost Installation Guide...
  • Page 16 To scroll through all of the advanced parameter codes and display the preferred code, press Down or Up. With the preferred parameter code displayed, press MENU to display the current parameter A421 Series Electronic Temperature Controls with Off-Cycle Defrost Installation Guide...
  • Page 17 Select a Defrost Interval (dI) value of 0. Select a dFt value between 1 minute and 99 minutes. - Select an SdF parameter value of 1 during normal On/Off operation to start a defrost cycle. A421 Series Electronic Temperature Controls with Off-Cycle Defrost Installation Guide...
  • Page 18 - Connect a momentary contact switch between BIN and COM on the T3 terminal block. - Each time the momentary contact switch is pressed, the defrost cycle starts or stops depending on whether the defrost cycle is running or not. See Figure 11. A421 Series Electronic Temperature Controls with Off-Cycle Defrost Installation Guide...
  • Page 19 HtS and LtS. See Figure 12. • The basic and advanced menus are not available. Only the Restricted Adjustment mode menu is available and only the OFF value can be adjusted. See Figure 14. A421 Series Electronic Temperature Controls with Off-Cycle Defrost Installation Guide...
  • Page 20 On or OFF value and the LtS value equal to the OFF or On value. Then the (On to OFF) control band is equal to the restricted adjustment range, LtS to HtS, and the OFF value cannot be adjusted in the restricted mode. A421 Series Electronic Temperature Controls with Off-Cycle Defrost Installation Guide...
  • Page 21: Troubleshooting

    To return to the Main screen, press Down and Up simultaneously. Figure 14: Adjusting temperature in the Restricted menu Troubleshooting A421 Series Controls display fault codes on the LCD as described in Table 4. Table 4: Fault codes Fault code Definition...
  • Page 22 If the measured values conform to the values in Figure 15, proceed to Step 3. g. If the sensor’s measured resistance value is substantially different from the expected value for that temperature, check the sensor wiring. If sensor wiring is correct, replace the sensor. A421 Series Electronic Temperature Controls with Off-Cycle Defrost Installation Guide...
  • Page 23 Johnson Controls/PENN distributor or sales representative. When you contact your Johnson Controls/PENN distributor, have the model number of the control available. You can find this number on the label inside the cover of the control.
  • Page 24 Ordering information See Table 5 to order a standard A421 Series Electronic Temperature Control. See Table 6 and Table 7 for more information about A99 sensors, mounting hardware, and other accessories used to install A421 Controls. Contact your nearest Johnson Controls or PENN distributor or sales representative to order these products.
  • Page 25: Technical Specifications

    Type 4X models: -40°F to 140°F (-40°C to 60°C), 0 to 95% RH noncondensing Shipping and storage: All models: -40°F to 185°F (-40°C to 85°C), 0% to 95% RH noncondensing Temperature control -40°F to 212°F or -40°C to 100°C range A421 Series Electronic Temperature Controls with Off-Cycle Defrost Installation Guide...
  • Page 26 4,000 V Ball pressure temperature 128°C Cover screw torque requirements All models: A421 [ ] E: To maintain type 4X / IP66 rating, instruction tighten enclosure screws to 10–12 in·lb A421 Series Electronic Temperature Controls with Off-Cycle Defrost Installation Guide...
  • Page 27 The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications Johnson Controls shall not be liable for damages resulting from misapplication or misuse of its products. A421 Series Electronic Temperature Controls with Off-Cycle Defrost Installation Guide...
  • Page 28 North American emissions compliance United States This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation.