Custom Energy Savings Settings
10 – TEMPERATURE RECOVERY TIME
00-60
for a HVAC unit to attain temperature as defi ned by Heat and Cool
"Recovery Temperature";
"Temperature Recovery Time" selected here and the actual
temperature recovery ability of the HVAC unit are used to calculate
setback temperatures. Calculated setback temperatures maximize
energy savings and at the same time ensure that a comfortable room
temperature (defi ned as Heat and Cool "Recovery Temperature") will
be restored within the selected "Temperature Recovery Time".
Setting the "Temperature Recovery Time" to "00", disables
temperature recovery. When temperature recovery is disabled,
thermostat will use the Minimum and Maximum Setback
Temperatures as setback set points.
30
(25* default setting) Select the maximum time allowed