6–4
Calibrating Your Module
Apply reference signal for offset
calibration to each channel to
be calibrated.
Set corresponding bits in the
calibration mask and set cal
Set cal–clk =1
NO
Cal–done = 1
NO
Bad–cal = 0
Exit
Cal–range = 0
Set cal–clk =0
NO
Cal–done = 0
Legend:
BTW = block transfer write
BTR
= block transfer read
Publication 1794-6.5.7 – April 1997

Flow Chart for Calibration Procedure

Hi/Lo = 0
BTW
BTW
BTR
?
YES
?
YES
BTW
BTR
?
YES
Apply reference signal for gain
calibration to each channel to
be calibrated.
Retain corresponding bits in
the calibration mask and set
cal Hi/Lo = 1
BTW
Set cal–clk =1
BTW
BTR
NO
Cal–done = 1
?
YES
NO
Bad–cal = 0
Exit
Cal–range = 0
?
YES
Set cal–clk =0
and
cal hi/lo = 0
BTW
BTR
NO
Cal–done = 0
?
YES
Clear corresponding bits in
the calibration mask
BTW