Configuration Of Connection Pipe - Inverter MINI SPLIT Owner's Manual And Installation Manual

High-wall ductless air conditioning & heating system
Table of Contents

Advertisement

1. Standard length of connection pipe
16,5ft (
) 25ft (
2. Min. length of connection pipe is 9,8ft (3m).
3. Max. length of connection pipe and max. high difference.
Max length
Cooling
of connec-
tion pipe
50ft (15
50ft (15
50ft (
66,5ft (20)
83,3ft (25)
4. The additional refrigerant oil and refrigerant charging required after prolonging
connection pipe
standard length, you should add 5ml of refrigerant oil for each additional
16,5ft (5m) of connection pipe.
of liquid pipe):
Additional refrigerant charging amount = prolonged length of liquid pipe ×
additional refrigerant charging amount per meter
the prolonged length of liquid pipe. The additional refrigerant
charging amount per meter is different according to the diameter of liquid
pipe. See the following sheet.
) 26,5ft (
)
Max height
difference
)
16,5ft (5)
)
16,5ft (5)
)
16,5ft (5)
33,3ft (10)
33,3ft (10)
40
Max length
Cooling
of connec-
tion pipe
8
3
3 ,
t f
1
0
0
t f
(30)
100ft (30)
100ft (30)
100ft (30)
16,5ft (
)
Max height
difference
(
)
33,3ft (10)
33,3ft (10)
66,5ft (20)
66,5ft (20)
66,5ft (20)

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MINI SPLIT and is the answer not in the manual?

Subscribe to Our Youtube Channel

Table of Contents

Save PDF