The 30 mA test current is also suitable to trip FI/RCD
!
with higher safety requirements (in bathrooms, pools,
etc.). The increased sensitivity of the safety function
of these FI/RCDs at e.g. 10 mA is not checked.
Information on maintenance and care
Clean all components with a damp cloth and do not use
cleaning agents, scouring agents and solvents. Store the
device in a clean and dry place.
Technical data
Voltage range
Frequency range
Indicator
FI/RCD test
Overvoltage category
Humidity
Degree of protection
Storage temperature
Operating temperature 0°C ... 40°C
Dimensions
Weight
Subject to technical alterations. 01.16
EU directives and disposal
This device complies with all necessary standards
for the free movement of goods within the EU.
This product is an electric device and must be
collected separately for disposal according to
the European Directive on waste electrical and
electronic equipment.
Further safety and supplementary notices at:
www.laserliner.com/info
LiveTester Plus
230 V ± 10%
Contact voltage threshold < 35 V AC
50 Hz
Error mode with 3 indicator lamps
LCD PE fault indicator
Indicator lamp RCD fault
Test current 30 mA ±15%
Test time 60 - 300 ms
CAT II – 300 V
Pollution degree 2
Max. 80% relative air humidity
(no condensation)
IP20
-10°C ... 70°C
76 x 67 x 69 mm (W x H x D)
76 g