Siemens SIPART PS2 6DR5xx0 series Compact Operating Instructions page 11

Electropneumatic positioners
Table of Contents

Advertisement

Note
Use of external NCS sensor / internal NCS module
If you use the accessory part "NCS sensor for contactless position measurement" or a built-in internal NCS module, the
locking and fixing measures described in this section are not necessary.
Overview diagram
NOTICE
Wrong detection of the rotary or part-turn movement
A different setting of the transmission ratio selector and the gear latch results in a hysteresis in position detection. The
hysteresis in position detection can result in unstable control behavior of the higher level control loop.
Make sure the transmission ratio selector
Gear latch
Locking transmission ratio to 33°
Neutral position
Locking transmission ratio to 90°
Transmission ratio selector
Figure 3-2
Locking friction clutch and transmission ratio
Requirements
● The positioner is mounted.
● You know whether the transmission ratio is to be set to 33° or 90°.
● The positioner has been commissioned successfully, i.e. initialization was completed with "FINISH".
12
and the gear latch
are set to the same value, either to 33° or to 90°.
Friction clutch
Friction clutch latch
Locking friction clutch
Release friction clutch
SIPART PS2 (6DR5...)
A5E03436620-AB, 01/2017

Advertisement

Table of Contents
loading

Table of Contents