VIII-A. General Maintenance

All electrical connections should be tightened every 3 months. Cooling fan motors are
permanently lubricated and do not require maintenance.
Although Swift-E load banks are designed with trouble-free operation in mind, some problems
can arise. Please consult the following table for solutions to the most common issues before
contacting a Simplex service representative.

VIII-B. Load Bank Wired to Source, but Won't Turn On

Ensure load bank is wired to source correctly. See
information about wiring your load bank to the source.
Set Meter Range Selector Switch to correct value for source voltage. See
11
for more information about setting up an operation.
Remove faceplate and make sure breaker is turned on. See
information about resetting the circuit breaker.
Check control fuses on front of load bank to ensure they aren't blown. See
17
to see where the fuses are located.
Remove faceplate and check loose relays, contactors, lugged wires, etc. See
page 9
for more information about inspecting the load bank.

VIII-C. Load Bank Overheating

Clear intake and exhaust vents of any debris. See
about the load bank's airflow needs.
Move load bank away from generator or other source's exhaust and walls and
other obstructions that restrict air flow. See
the load bank's airflow needs.
Make sure ambient temperature isn't too high to allow for cool air flow. See
for more information about overheating failures.

VIII-D. Meter Displaying Unexpected Results

Ensure Current Transformer Ratio is set correctly (100:5 for Swift-E, 150:5 for
Swift-E+). See
Remove all power from the load bank and all dan/control power before servicing the
load bank. Never operate or service a load bank that is not grounded.
VIII. TROUBLESHOOTING
for more information about setting up your meter.
8 June 2018 • Simplex Service 800-637-8603 • Page 16 of 19
Swift-E / Swift-E+ Load Bank Manual
page 10
for more
page 13
for more
for more information
for more information about
page
page

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SWIFT-E+ and is the answer not in the manual?

Subscribe to Our Youtube Channel

This manual is also suitable for:

Swift-e

Table of Contents