5a) Initial Harvest Cycle – LEDs 1, 4, and 2 are on. WV and X11 relay continue. Comp,
FMR, HGV, and X10 relay energize. CB monitors the warming of the evaporator via the
thermistor located on the suction line. When the thermistor reaches 48°F (9°C), CB
reads 3.9 kΩ from the thermistor and turns harvest termination over to the harvest timer
(S4 dip switch 1 & 2). The harvest timer has settings of 60, 90, 120, and 180 sec. The
pump-out timer (S4 dip switch 3 & 4) acts in place of the harvest timer during cycles
with a pump-out (S4 dip switch 5 & 6). WV and X11 relay are energized during harvest
for a maximum of 6 min. or the length of harvest minus 50 sec., whichever is shorter.
50 sec. before harvest terminates, PM energizes. See step 5b below.
a) Comp Diagnosis: Check that evaporator is warming. If not, confirm that Comp
energizes. If not, check for 115VAC at CB K1 #1 (V) or #9 (V) to neutral (W).
If 115VAC is not present, check for 115VAC at CB K1 #7 (BR) or #10 (BR) to neutral
(W). If 115VAC is present at #7 (BR) or #10 (BR) and not at #1 (V) or #9 (V), replace
CB. If 115VAC is present, check for 115VAC at CR or MC solenoid. If 115VAC is
present, confirm contacts are closed. If not, replace CR or MC. If CR or MC contacts
are closed, check Comp external overload, Comp start and run capacitors, Comp
start relay, and Comp motor winding. If Comp is energized and evaporator is not
warming, check that HGV energizes and opens. Check for 115VAC at CB K1 #2 (P)
to a neutral (W). If 115VAC is not present and LED 2 is on, replace CB. If 115VAC is
present, check coil voltage and continuity. Replace as needed. Confirm that LLV is
de-energized and closed (not bypassing). If energized, replace CB. If de-energized
and bypassing, replace LLV. Confirm WRV is not leaking by. If evaporator is warming,
PM energizes for the last 50 sec. of harvest.
b) HGV Diagnosis: If Comp is energized and evaporator is not warming, check that
HGV energizes and opens. Check for 115VAC at CB K1 #2 (P) to neutral (W).
If 115VAC is not present, replace CB. If 115VAC is present, check for 115VAC at HGV
coil and check HGV coil continuity. Replace as needed.
c) LLV Diagnosis: Confirm that LLV is de-energized and closed (not bypassing).
If energized, replace CB. If de-energized and bypassing, replace LLV.
d) WRV Diagnosis: Confirm WRV is not leaking by.
5b) Harvest Pump Timer – LEDs 1, 3, and 2 are on. When the thermistor reaches 48°F
(9°C), CB reads 3.9 kΩ from the thermistor and turns harvest termination over to the
harvest timer (S4 dip switch 1 & 2). 50 sec. before the harvest timer terminates, LED
3 turns on and PM energizes. Comp, FMR, HGV, and X10 relay continue. LED 4 turns
off, WV and X11 relay de-energize.
Diagnosis: Place a thermometer on the suction line next to the thermistor. Has it
warmed to 48°F (9°C) or warmer? Confirm thermistor status. See "II.F. Thermistor
Check." If the thermistor reading is in proper range, dip switch 7 is on, and PM does
not energize 50 sec. before harvest terminates, replace CB. If WV continues, check for
115VAC at CB K1 #6 (O). If 115VAC is present, and LED 4 is off, replace CB. If LED 3 is
on and PM is not energized, check for 115VAC at CB K1 #5 (DBU). If 115VAC is not
present, replace CB. If 115VAC is present and PM is not energized, check for 115VAC
at X10 relay terminal #7 (Y) to neutral (W). If 115VAC is not present, check for 115VAC
at X10 relay terminal #3 (P) to neutral (W) and X10 relay terminal #5 (Y) to neutral (W).