Daikin FDYB30CV1M User & Installation Manual

Daikin FDYB30CV1M User & Installation Manual

R22 split series

Advertisement

INSTALLATION
MANUAL
R22 Split Series
Models
FDYM30CV1M
FDYM40CV1M
FDYM60CV1M
FDYM71CV1M
FDYM80CV1M
FDYM90CV1M
FDYM90CV1M
FDYM100CV1M
FDYM125CV1M
FDYM125CV1M
FDYM140CV1M
FDYM160CV1M
FDYB30CV1M
FDYB40CV1M
FDYB60CV1M
FDYB71CV1M
FDYB90CV1M
FDYB90CV1M
FDYB125CV1M
FDYB125CV1M
FDYB140CV1M
FDYB160CV1M
RY30CV1M
RY40CV1M
RY60CV1M
RY71CV1M
RY80CV1M
RY90CV1M
RY90CY1M
RY100CV1M
Cерия R22 с раздельной установкой
RY125CV1M
RY125CY1M
RY140CY1M
RY160CY1M
Installation Manual
R22 Split series
Manuel d'installation
Série split R22
Руководство По Установке
Kurulum Kılavuzu
R22 Split serisi
English
Français
Русский
Türkçe

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the FDYB30CV1M and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Daikin FDYB30CV1M

  • Page 1 INSTALLATION MANUAL R22 Split Series Models FDYM30CV1M FDYB30CV1M RY30CV1M Installation Manual FDYM40CV1M FDYB40CV1M RY40CV1M English R22 Split series FDYM60CV1M FDYB60CV1M RY60CV1M FDYM71CV1M FDYB71CV1M RY71CV1M FDYM80CV1M RY80CV1M Manuel d’installation Français Série split R22 FDYM90CV1M FDYB90CV1M RY90CV1M FDYM90CV1M FDYB90CV1M RY90CY1M Руководство По Установке...
  • Page 2 OUTLINE AND DIMENSIONS Indoor Unit All dimensions are in mm/(in) Model FDYM30CV1M 212,8 114 FDYB30CV1M (1,2) (29,2) (27,6) (26,1) (0,4) (30,1) (2,8) (10,3) (16,2) (13,8) (8,9) (8,3) (9,1) (8,4) (4,5) FDYM40CV1M 212,8 114 FDYB40CV1M (1,2) (34,7) (33,1) (31,6) (0,4) (35,6) (2,8) (10,3) (16,2) (13,8) (8,9) (8,3) (9,1)
  • Page 3 Outdoor Unit All dimensions are in mm/(in) (1,2) Dimension RY30CV1M RY40CV1M (27,5) (20,5) (9,8) (19,1) (6,8) (1,4) (3,7) (3,6) (3,3) (2,6) (17,3) (5,1) (4,3) (0,5) (0,7) Outdoor Unit All dimensions are in mm/ (in) Dimension RY60CV1M (33,7) (24,7) (12,9) (20,0) (7,1) (1,7) (3,7) (5,9)
  • Page 4 Outdoor Unit All dimensions are in mm/(in) Model RY90CV1M/ RY90CY1M/ 1030 448 141,5 746,5 RY100CV1M/ RY125CV1M/ (40,6) (33,5) (15,7) (15,4) (16,3) (32,6) (2,8) (7,7) (3,6) (19,2) (17,6) (5,6) (29,4) (3,2) RY125CY1M/ RY140CY1M...
  • Page 5 All dimensions are in mm/(in) Model RY160CY1M 1030 448 746,5 320 141.5 (40,6) (33,5) (15,7) (17,6) (29,4) (12,6) (1,0) (2,0) (3,3) (1,6) (5,6) (0,8) (2,4)
  • Page 6: Safety Precautions

    INSTALLATION MANUAL This manual provides the procedures of installation to ensure a safe and good standard of operation for the air conditioner unit. Special adjustment may be necessary to suit local requirements. Before using your air conditioner, please read this instruction manual carefully and keep it for future reference. SAFETY PRECAUTIONS ! WARNING ! CAUTION...
  • Page 7 Respect the installation clearance. FDYM30CV1M Do not put the indoor unit where there is direct sunlight on unit. FDYB30CV1M The location is suitable for piping and drainage and it must be FDYM40CV1M have a large distance between a door and unit.
  • Page 8: Refrigerant Piping

    As a result, compressor reliability will be affected. Always choose the shortest path and follow the recommendation as tabulated below: Model FDYM30CV1M FDYM40CV1M FDYM60CV1M FDYM71CV1M FDYM80CV1M Data FDYB30CV1M FDYB40CV1M FDYB60CV1M FDYB71CV1M Maximum Length, A m (ft) 12 (39.4) 12 (39.4) 15 (49.2) 15 (49.2) 15 (49.2)
  • Page 9 Piping Works And Flaring Technique Piping Connection To The Units Do not use contaminated or damaged copper tubing. If any Align the center of the piping and sufficiently tighten the flare piping, evaporator or condenser had been exposed or had been nut with fingers.
  • Page 10 Voltage range 220V–240V /1Ph /50Hz + ! Recommended fuse* Power supply cable size* Number of conductors Interconnection cable size* Number of conductors FDYM30CV1M/ FDYB30CV1M - RY30CV1M Outdoor Coil Sensor FDYM40CV1M/ FDYB40CV1M - RY40CV1M FDYM60CV1M/ Terminal Strip FDYB60CV1M - RY60CV1M Outdoor Unit...
  • Page 11 Outdoor Coil Sensor FDYM90CV1M/FDYB90CV1M - RY90CV1M FDYM100CV1M - RY100CV1M FDYM125CV1M/FDYB125CV1M - RY125CV1M COMP Terminal Strip Terminal Strip Indoor Unit COMP Outdoor Unit There must be a all pole switch with a minimum 3 mm contact gap and fuse / circuit breaker as Power Supply Cable recommended in the fixed installation circuits.
  • Page 12 PURGING THE REFRIGERANT PIPING Purging The Piping And The Indoor Unit • Close the manifold valve and stop the vacuum pump. • On the outdoor unit, open the suction and liquid valve (anti Except the outdoor unit which is pre-charged with refrigerant, clockwise) with 4 mm key for hexagon sacked screw.
  • Page 13: Additional Charge

    • When the required refrigerant quantity is pumped in the unit, close the low pressure manifold and the gas cylinder valve. • Disconnect the manometer and the gas cylinder. Place back the service port cap. Additional Charge Heat Pump Unit Indoor FDYM30CV1M FDYM40CV1M FDYM60CV1M FDYM71CV1M FDYM80CV1M FDYB30CV1M FDYB40CV1M FDYB60CV1M FDYB71CV1M Outdoor RY30CV1M RY40CV1M RY60CV1M RY71CV1M RY80CV1M...
  • Page 14 SPECIAL PRECAUTIONS WHEN CHARGING UNIT WITH SCROLL COMPRESSORS These precautions are intended for use with Scroll compressors only with R22, R407C, R134A, R404A, R507 and R410A refriger- ants but are not applied to other compressors. Scroll compressors have a very high volumetric efficiency and quickly pump a deep vacuum if there is insufficient refrigerant in the system or if refrigerant is added too slowly.
  • Page 15: Overall Checking

    OVERALL CHECKING Ensure the following, in particular:- 2. Watch out for the following:- 1. The unit is mounted solidly and rigid in position. Is the electric plug firmly inserted into the socket? 2. Piping and connections are leak proof after charging. Is there any abnormal sound from unit? 3.
  • Page 16: Service And Maintenance

    AUTO RANDOM RE-START FUNCTION If there is a power cut when the unit is operating, it will automatically resume the same operating mode when the power is restored. (Applicable only to units with this feature). SERVICE AND MAINTENANCE Service Parts Maintenance Procedures Period Indoor Air Filter...
  • Page 17: Troubleshooting

    TROUBLESHOOTING When any malfunction of the air conditioner unit is noted, immediately switch off the power supply to the unit. Check the following fault conditions and causes for some simple troubleshooting tips. Fault Causes 1. The compressor does not start operate after 3 minutes - Protection against frequent starting.

Table of Contents