Outdoor Unit SL Series Clearance (in mm)
300
Note: If the obstacle is higher than 2 m or if there is any obstruction at the upper part of the unit allow more space than indicated in
the table above.
Maximum Pipe Length And Maximum Number Of Bends
When the pipe length becomes too long, both the capacity and reliability drop. As the number of bends increases, system piping
resistance to the refrigerant flow increases, thus lowering the cooling capacity. As a result, compressor reliability will be affected.
Always choose the shortest path and follow the recommendation as tabulated below:
Model
Data
Maximum Length, A m (ft)
Maximum Elevation, B m (ft)
Maximum No. of Bends, C
Model
Data
Maximum Length, A m (ft)
Maximum Elevation, B m (ft)
Maximum No. of Bends, C
A
C
1000
Discharge
Air

REFRIGERANT PIPING

FDYM30CV1M
FDYM40CV1M
FDYB30CV1M
FDYB40CV1M
12 (39.4)
12 (39.4)
5 (16.4)
5 (16.4)
10
10
FDYM90CV1M
FDYM100CV1M
FDYB90CV1M
45 (147.6)
45 (147.6)
25 (82.0)
25 (82.0)
10
10
B
The location must be well-ventilated, so that the unit can draw
in and distribute plenty of air thus lowering the temperature.
A place capable of bearing the weight of the outdoor unit as
well as isolating noise and vibration.
A place protected from the direct sunlight. Use an awning for
protection if necessary.
The installation location must not be susceptible to highly
concentrated dust, oil, salt or sulfide gas.
300
FDYM60CV1M
FDYM71CV1M
FDYB60CV1M
FDYB71CV1M
15 (49.2)
8 (26.2)
10
FDYM125CV1M
FDYM140CV1M
FDYB125CV1M
FDYB140CV1M
45 (147.6)
25 (82.0)
10
C
A
C
3
500
Service
Access
FDYM80CV1M
15 (49.2)
15 (49.2)
8 (26.2)
8 (26.2)
10
10
FDYM160CV1M
FDYB160CV1M
45 (147.6)
35 (114.8)
25 (82.0)
15 (49.2)
10
10
B