Mounting The Epm P40N Plus Led External Display - GE Grid Solutions Multilin 9450 Instruction Manual

Advanced power quality metering system
Table of Contents

Advertisement

PLUS
MOUNTING THE EPM P40N
3.2
Mounting the EPM P40N
Note
3–4
LED EXTERNAL DISPLAY
PLUS
LED External Display
The EPM 9450/9650 LED display (model number PL9000-P40NPLUS0) mounts using a
standard ANSI C39.1 drill plan.
Secure the four mounting studs to the back of the panel with the supplied nuts.
Six feet of RS485 communication/power cable harness is supplied. Allow for at least a
1.25-inch (3.17cm) diameter hole in the back for the cable harness. See Chapter 5 for
communication and power supply details.
The cable harness brings power to the display from the EPM 9450/9650 meter, which
supplies 15–20V DC. The P40N
Figure 3-3: ANSI C39.1 Drill Plan for P40N
The P40N shown below is a legacy product, and not intended for new applications.
EPM 9450/9650 ADVANCED POWER QUALITY METERING SYSTEM – INSTRUCTION MANUAL
PLUS
can draw up to 500mA in display test mode.
4.38" Sq.
(11.12 cm)
P40N Front Dimensions
Figure 3-4: Legacy P40N Dimensions
CHAPTER 3: HARDWARE INSTALLATION
PLUS
Display
.75"
(1.91
1.438" Sq.
cm)
(3.65 cm)
P40N Side Dimensions