CHAPTER 9: EXTERNAL I/O MODULES
9.6

Analog Input Modules

9.6.1
Overview
EPM 9450/9650 ADVANCED POWER QUALITY METERING SYSTEM – INSTRUCTION MANUAL
Model Numbers
Accuracy
Scaling
Communication
Power Requirement
Operating Temperature
Maximum Load
Impedance
Factory Settings
Default Settings (Reset
Button)
The Analog Input Modules (0 ±1mA, 0 ±20mA, 0 ±5Vdc and 0 ±10Vdc) are available in 8-
channel format. Maximum registers per request, read or write, is 17 registers.
The EPM 9450/9650 meter supplies power for up to 4 connected Analog Input modules.
See Section 9.2 for power and communication details. Refer to Section 5.6.2 to determine if
you must use an additional power source, such as GE's PSIO.
All inputs share a single common point. This is also an isolated connection (from ground).
The Modbus Map for the Analog Output Module (and operating details) can be found in the
Modbus Communicating I/O Modules Manual.
Table 0
Analog Input Module Specifications
8AI1: 8-channel analog input 0 ±1mA
8AI2: 8-channel analog input 4-20mA
8AI3: 8-channel analog input 0 ±5VDC
8AI4: 8-channel analog input 0 ±10VDC
0.1% of Full Scale
Programmable
RS485, Modbus RTU
Programmable Baud Rates: 4800, 9600, 19200, 38400, 57600
15-20VDC @50-200mA; EPM 9450/EPM 9650 support up to four
modules
o
o
(-20 to +70)
C/(-4 to +158)
F
0 ±1mA: 10k Ohms; 4-20mA: 500 Ohms
Modbus Addresses:
8AI1: 136
8AI2: 140
8AI3: 144
8AI4: 148
Baud Rate: 57600
Transmit Delay Time: 0
Modbus Address: 247
Baud Rate: 57600
Transmit Delay Time: 20msec
ANALOG INPUT MODULES