Mj-Xl Self Testing; Communications Module Troubleshooting - Siemens MJ-XL Installation And Operation Manual

Voltage regulator control panel
Hide thumbs Also See for MJ-XL:
Table of Contents

Advertisement

Note: If password protection is in effect, you must
enter the password to enable calibration. The
default password for the <DIAGNOSTICS>
Menu is "3333".
Voltage and Current Calibration
Table 8.2
Signal to
Test Signal
Calibrate
Application
Point
U2
U2 to E
(P2A-8 & 6)
P2
P2 to E
(P2A-4 & 6)
C/C2
C2 to E1
Low
(P2A-5 & 7)
C/C2
C2 to E1
Medium
(P2A-5 & 7)
C/C2
C2 to E1
High
(P2A-5 & 7)
Note 1: Prior to calibration, disconnect panel from regulator, and remove on-board jumper J1 (see Figure J.1) and Terminal Strip jumper at
P3B-11 & 12. After calibration, replace J1 and Terminal Strip Jumper at P3B-11 & 12.
L
8.5
MJ-X
Self Testing
L
After reset, the MJ-X
runs through an internal diagnostics
routine. The start-up diagnostics routine includes a front
panel indicator test— the LED indicators simultaneously
flash three times so that an operator can verify them. Dur-
ing the LED test, the MJ-X
front panel screen.
The start-up diagnostics routine consists of several checks
and internal tests, including a ROM (program memory)
checksum calculation. The MJ-X
the checksum test (PASS or FAIL) in the "Checksum="
item under the <DIAGNOSTICS> Menu.
Siemens Power Transmission & Distribution, Inc.
8
MJ-XL Control Panel Basic Troubleshooting
Test Signal
Measurement
Calibration Signal
Point
Voltage Calibration
Terminals
Voltage Calibration
Terminals
C/C2
(P3B-11 & 12)
C/C2
(P3B-11 & 12)
C/C2
(P3B-11 & 12)
L
displays "Testing..." on the
L
displays the results of
Repeat the above procedure for C/C2 Medium and C/C2
High. After calibration, replace J1 and Terminal Strip
jumper at P3B-11 & 12.
Nominal
Tolerance
Magnitude
±
120 VAC (RMS)
0.5 VAC
±
120 VAC (RMS)
0.5 VAC
±
5 mA (RMS)
0.2 mA
±
80 mA (RMS)
0.5 mA
±
140 mA (RMS)
0.7 mA
A checksum failure indicates a problem with the unit. A
checksum or other self-test failure will activate the "Self
Test Fault" alert. If this alert occurs, contact your Siemens
Power Transmission & Distribution representative for
instructions.
8.6
Communications Module
Troubleshooting
In the <DIAGNOSTICS> Menu, the MJ-X
provides data items for testing the Communications Mod-
ule and verifying its operation. Please refer to the MJ-X
Communications Module Installation Manual for verifying
the Communications Module operations using the
<DIAGNOSTICS> Menu data items.
L
MJ-X
Data Item
Conditions
<DIAGNOSTICS>
Menu
U2 Cal
U2/P2 key
= U2
P2 Cal
U2/P2 key
= P2
C/C2low
Note 1
C/C2med
Note 1
C/C2high
Note 1
L
Control Panel
L
51