Communications Definition- The <Communications> Menu - Siemens MJ-XL Installation And Operation Manual

Voltage regulator control panel
Hide thumbs Also See for MJ-XL:
Table of Contents

Advertisement

4
Setting Up the MJ-XL Control Panel
passwords can only be changed or reset after you enter
the Level 2 password for that Menu.
Entering passwords
You can go directly to the <PASSWORD> menu and enter
the password(s) you want, or when viewing a specific
menu item, press Cancel/Reset or Change. If password
protection is enabled for this menu, you are prompted to
enter the password. (If you see the password prompt, skip
step 1 below.)
1.
Use the Menu and Scroll keys to view the <PASS-
WORD> Menu. Press the Ú key. The display screen
responds: "Enter PW xxxx".
2.
Press the Change key. The display screen responds
by flashing "n" in the leftmost position of the four
character password field. This represents the charac-
ter to be entered.
3.
Use the Ù and Ú keys to step through the alpha and
numeric characters until the desired character is pre-
sented in the display screen.
4.
Press the Ø key to move the cursor to the next char-
acter to the right, and so on until all four characters of
the password have been entered.
5.
When you have completed entering the password,
press the Save key.
(If you started in the <PASSWORD> menu, go to step 6.
Otherwise, go to step 7.)
6.
If you entered a valid password, the MJ-X
plays "PW Accepted", and then displays "Enter PW".
This allows you to enter additional passwords. (You
may wish to enter additional passwords if, for exam-
ple, you have enabled both Level 1 and Level 2; or if
you have enabled Level 2 and have different pass-
words for each Menu.) When you have entered all
passwords, you can use the Menu and Scroll keys to
view the data item(s) you wish to change or reset.
Skip step 7.
7.
If you enter the correct password, the MJ-X
displays, "PW Accepted" and then returns to the
screen you were viewing when you started this pro-
cess. If you enter a valid password, but not the cor-
rect password for this menu, the MJ-X
"Enter PW:" again. This process repeats until you
enter the correct password for this menu.
Once a password has been accepted, changes and resets
are permitted for the remainder of the session. To end the
session, view End Session in the <PASSWORD> Menu,
and use the Change, Scroll, and Save keys to change the
default N(o) to Y(es). If you leave the session enabled
(un-terminated) the MJ-X
when the screen time-out period expires (see <CONFIG-
URE> Menu Screen t.o. data item).
30
L
briefly dis-
L
briefly
L
displays
L
automatically terminates it
4.7
Communications Definition—
the <COMMUNICATIONS> Menu
The <COMMUNICATIONS> Menu provides data items
for setting up local communications and remote communi-
cations via the Communications Module. These data
items are described in the following sections.
4.7.1
Setting Up the Local Data Port
The Local Data Port must be set up for proper operation.
The <COMMUNICATIONS> Menu contains the Data Port
setup items described in Table 4.7:
Table 4.7 <COMMUNICATIONS> Menu Setup Data
Items
DATA ITEM
DESCRIPTION
DatPortBaud:
Local Data Port
transmission rate
Data Parity:
Local Data Port
Parity Setting
DataPorAddr:
Enables/Disables
Addressing for
Data Port
Reg Id:
Regulator Identifi-
cation Number
(Note that this is
NOT the address
for Data Port Com-
munications.)
Comm Addr:
2200 protocol
address for the
specific unit
Note: Default values shown in bold type.
To change the baud rate for the data port, view DatPort-
Baud under the <COMMUNICATIONS> Menu and select
one of the options (300, 600, 1200, 4800, 9600, or
19,200).
To change the parity for the data port, view Data Parity
under the <COMMUNICATIONS> Menu and select one
of the options (EVEN or NONE).
To enable or disable addressing for the data port, view
DataPortAddr under the <COMMUNICATIONS> Menu
and select one of the options (OFF or ON.)
addressing for local communications with MJXplorer or a
Data Reader. Enable addressing for multi-drop communi-
cations (see MJ-X Application Note 5, MJ-X Data Port to
MJXplorer Communications via Modem, for details).
To change the Regulator Identification, view Reg Id under
the <COMMUNICATIONS> Menu and set the desired
Reg Id value. For extracting data and generating reports
using the Data Reader and Data Reader software, the Reg
Id value appears prominently at the top of the Data Reader
reports. If using the Data Reader, select a different value
L
of Reg Id for each MJ-X
interfacing to a Data Reader, refer to MJ-X Application
Siemens Power Transmission & Distribution, Inc.
INPUTS
300, 1200, 2400,
4800, 9600, or
19200
EVEN, NONE
OFF, ON
NNNNN
(Range 0-32765)
NNN
(Range 0-255
See Table 4.8)
Disable
unit. (For more information on

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents