Hcp Used As A Telephone Zone; Hcp As (70.7V/25V) Speaker Zone In An Xlsv System - Siemens HCP Installation Instructions Manual

Intelligent control point
Table of Contents

Advertisement

LINE 1
FROM DLC DEVICE
LOOP IN CC-5 / CC-2
LINE 2
POWER LIMITED
PROGRAMMING
HCP DC SUPPLY
FROM PSC-12 (TB-3),
PSX-12 (TB-3),
OR PAD-4* (TB16)
ELECTRICAL:
INPUT DC SUPPLY: 18.8 - 28.2VDC,
30mA MAX
FILTERED FULL WAVE
*REFER TO PAD-4 INSTALLATION INSTRUCTIONS, P/N 315-050217, FOR PROPER SETTING OF SWITCH 4. THE AUXILIARY POWER OUTPUT MUST BE CONFIGURED TO "ALWAYS ON".
Figure 6

HCP Used As A Telephone Zone

HCP As (70.7V/25V) Speaker Zone in an XLSV System

Siemens Industry, Inc.
Building Technologies Division
SUPERVISED, 24 OHMS MAX
UNSHIELDED, USE TWISTED PAIR
1
2
3
4
5
6
+
POINTS
HCP
SHIELD
TO
6
5
4
3
2
1
EARTH
SHIELD
SHIELD
FROM PREVIOUS HCP OR TZC-8B
(100 OHMS MAXIMUM
LINE RESISTANCE)
COMMON TALK RISER
(POWER LIMITED)
SEE TZC-8B INSTALLATION
INSTRUCTIONS, P/N 315-034110,
FOR RISER RATINGS
When the HCP is used as a speaker zone (FireFinder-XLS System only), the 24 VDC
provides power to the supervision circuitry. If the 24 volts is lost or there is an open
or shorted speaker output line, a trouble condition displays on the PMI/PMI-2 of the
FireFinder-XLS.
The 70.7V/25V RMS audio input to the HCP must be power limited, such as from the
ZAC-40. The ZAC-40 supervises the audio connection path to the HCP and provides
up to 40 watts of power. The ZAC-40 can be wired Style Y (Class B) only. Refer to the
ZAC-40 Installation Instructions, P/N 315-035400 for further information. In order to
function properly during degrade mode, the DLC to which the HCP is connected
must be located in the same enclosure as the DAC-NET and ZAC-40 that supply
audio to the HCP .
When the HCP is used as a speaker zone, the output speaker lines are only super-
vised when the zone is not active. The audio output must not be allowed to exceed
25 watts. The approximate decibel loss for the total speaker zone wire length for
various wire gauge sizes is shown in Figure 7 for the 70.7V option and in Figure 8 for
the 25V option. Connect the speaker output as Style Y (Class B) as shown in Figure 9.
1
FJ-303
PROGRAMMING
POINTS
HCP
FJ-303
SHIELD
TO
6
EARTH
75K, ¼W, +/-5%
SHIELD
EOL RESISTOR
P/N 140-050797
AT LAST FJ-303
*
REMOVE
ALL
10K TERMINATING RESISTORS FROM THE FJ-303s
6
POSITIVE AND NEGATIVE GROUND FAULT
DETECTED AT <500 OHMS FOR
TERMINALS 3-6 ON TB1.
USE TWISTED PAIR
2
3
4
5
6
+
WARDEN'S STATIONS
(FTS SERIES)
5
4
3
2
1
75K, ¼W, +/-5%
EOL RESISTOR
P/N 140-050797
AT LAST STATION
NOTES:
1. THE SHIELD ON THE COMMON TALK
10K, 1/2W, +/-5%
LINE MUST BE CONTINUOUS AND
EOL RESISTOR
CONNECTED ONLY TO EARTH
GROUND AT CONTROL PANEL.
2. ALL WIRING MUST COMPLY WITH
NATIONAL AND LOCAL CODES.
3. 12-18 AWG OR AS REQUIRED
BY THE LOCAL AUTHORITY
HAVING JURISDICTION.
P/N 315-034860-13
SUPERVISED
24 OHMS MAX
UNSHIELDED