Chapter 3: Mounting and Wiring

Resolver Module (FMIR01)

The resolver module has an eight-position connector. (See Figure 3-5). The terminal wire size
for all positions is No. 22-12 AWG. The reset-to-preset input is an edge sensitive input that
resets position data to a preprogrammed value. An open collector sinking device or dry contact
applied to these terminals activates the input. For programming of reset-to-preset value, see
Chapter 4: Programming.
Reset-to-Preset
Input
Variable Pulse LDT Module (FMIP01) Input Option V1
The variable pulse LDT module has an eight-position connector. It is only necessary to connect
your LDT to positions 1 through 4. (See Figure 3-6). Positions 1 and 2 provide +24 VDC to
power the LDT. Positions 3 and 4 are used for the LDT's pulse-width output signals. These
signals comprise an RS-422 differential input. Positions 5-8 are provided for future expansion.
The terminal wire size for all positions is No. 22-12 AWG. This module should only be used
with Gemco LDT model 951VP-2110 transducers. An open collector sinking device or dry
contact applied to the Reset to Preset terminals activates the input.
12
Spec Tech Industrial Electric
www.spectechind.com
RH
RL
S3
S1
S2
S4
Input +
{
Input -
(See wiring
diagram for
ratings)
Figure 3-5 Resolver Pinout Diagram
+24VDC @135mA
GROUND
PROBE VP+
PROBE VP -
GROUND
Aux 24VDC @15mA
Input +
{
Reset-to-Preset
Input
Input -
Figure 3-6 Variable Pulse LDT Pinout
Diagram Input Option V1
Installation and Programming Manual
www.spectechind.com
888-773-2832
RSLVR
FMIR01
PROBE
FMIP01
888-773-2832