Chapter 3: Mounting and Wiring

3.2: Wiring

This section contains pinout diagrams for each module. System wiring diagrams follow.

Controller Module (FMMP01)

The controller has two connectors: a D9 connector (J1) for RS-232 and RS-485 serial
communications, and a program lockout connector (J2) intended for a keyswitch. (See Figure
3-2). Making connections to both connectors is optional. However, the program lockout
connector must be jumpered to allow the unit to enter program mode. J2's input rating is +5
VDC maximum dry contact or open collector (drain) only. Actuation voltage must be less than
+1.0 VDC at 0.2 mA. The terminal wire size is No. 22-12 AWG.
COMMUNICATIONS CONNECTOR
PIN SIGNAL NAME DIRECTION
1
GND CHASSIS
2
RXD RS-232
3
TXD RS-232
4
NO CONNECTION
5
GND SIGNAL
6
TX2+ RS-485
7
RTS RS-232
8
CTS RS-232
9
TX2- RS-485
NOTE: The controller's program lockout connector (J2) must be jumpered to allow the unit
to enter program mode.

Relay Output Module (FMOR01)

The relay output module contains two overtravel limit relays. Each relay contains a N.O. contact
pair and a separate N.C. contact pair. (See Figure 3-3). The relay contacts are rated at 8 amps
250 VAC, 30 VDC, 1/4 HP 125, 250 VAC. The terminal wire size is 22-12 AWG.
10
Spec Tech Industrial Electric
www.spectechind.com
OUTPUT
COMMUNICATIONS (J1)
INPUT
CONNECTOR D9 FEMALE
I / O
(J2)
INPUT
OUTPUT
I / O
Figure 3-2 Controller Pinout Diagram
Drawing E8002099
Installation and Programming Manual
www.spectechind.com
PIN 9
PIN 6
{
INPUT +
INPUT -
FMMP01
888-773-2832
C.P.U.
PIN 5
PIN 1
888-773-2832