ZS zone sensors
ZS Standard
Specifications for ZS zone sensors
Specifications for ZS zone sensors
Sensing element
accuracy
Temperature
Humidity
CO
2
VOC
CO
sensor type
2
ZS Plus
ZS Pro
Temperature only:
32° to 122°F (0° to 50°C):
±0.36°F (0.2°C)
10% to 90%: ±1.8% typical. Less than 0.5% drift per year.
400 to 1250 PPM: ±30 PPM or 3% of reading, whichever is greater
1250 to 2000 PPM: ±5% of reading plus 30 PPM
See CO
sensor installation (page 10).
2
0 to 2,000 CO2 PPM Equivalent: ±100PPM
Non-Dispersive Infrared (NDIR)
AURORA UPC ZS ZONE SENSORS INSTALLATION GUIDE
ZS Pro with
motion sensor
Temperature if humidity is included:
50° to 104°F (10° to 40°C):
±0.54°F (0.3°C)
9
ZS Pro-F
Need help?
Do you have a question about the UPC ZS ZONE SENSOR and is the answer not in the manual?