Co2 Sensor Installation; Motion Sensor Installation; To Address A Zs Zone Sensor - Aurora UPC ZS ZONE SENSOR Installation Manual

Universal protocol converter
Table of Contents

Advertisement

ZS zone sensors

CO2 sensor installation

IMPORTANT Do not install ZS CO
maintain accuracy, it must be installed only in a zone that is unoccupied for at least 4 hours a day with enough air
movement during the unoccupied period to return CO
A ZS sensor with CO
that deviates no more than 40PPM for at least 15 minutes, and assigns that value to the 400PPM baseline. This
daily Automatic Background Calibration may take up to 21 days to fully calibrate the sensor.
NOTE Dropping a sensor can upset the calibration, and it may require 21 days to return to our stated accuracy.

Motion sensor installation

The motion sensor on a ZS Pro needs to have a direct line of sight to the occupants in the room.
If the size of the room exceeds the maximum detector range, use multiple sensors to adequately monitor the area.
Avoid placing the sensor:
In a location that has a direct line of sight through an open door to a hallway where the sensor could detect
movement of people in the hallway.
Near air ducts. Rapidly changing air currents from the air ducts could lead to false sensor readings.
Specifications for ZS zone sensors

To address a ZS zone sensor

Each ZS Sensor on an Rnet must have a unique address, but addresses do not have to be sequential.
Use the DIP switches on the back of the ZS zone sensor to set an address from 0 to 14. (0 is factory default.) Each
DIP switch has the value shown in the figure below. Turn on as many DIP switches as you need so that their total
value equals the address.
DIP
Switch
value
1
2
4
8
sensors in continuous occupancy applications. For a ZS CO
2
uses Automatic Background Calibration which waits for the lowest value in a 24-hour period
2
EXAMPLE DIP switches 1 and 4 above
are on. Their values (1 + 8) total 9, so
the sensor's address is 9.
AURORA UPC ZS ZONE SENSORS INSTALLATION GUIDE
to background levels.
2
11
sensor to
2

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the UPC ZS ZONE SENSOR and is the answer not in the manual?

Subscribe to Our Youtube Channel

Table of Contents