F5 & F15 Series Service and Installation Manual
Installation: Self-Contained F15 Series
Location
Units represented in this manual are for indoor use only. Be
sure the location chosen has a floor strong enough to support
the total weight of the cabinet and contents. A fully loaded model
may weigh as much as 3,000 pounds! Reinforce the floor as
necessary to provide for maximum loading.
For the most efficient refrigeration, be sure to provide good air
circulation inside and out. Don't pack the refrigerator so full
that air cannot circulate. Be sure that the exterior of the unit has
access to ample air. Avoid hot corners and locations near stoves
and ovens.
Unit is designed to maintain 36°F (2°C) to 40°F (4°C) interior
cabinet temperature at 55% or lower ambient relative humidity.
Leveling
A level cabinet looks better and will perform better because
the drain pan will drain properly, the doors will line up with
the frames properly and the cabinet will not be subject to
undue strain. Units come standard with adjustable legs and
bullet feet to make leveling easier. If your unit has casters,
install in a stable condition with the front casters locked before
operating.
Installation: Remote F15 Series
D
1.00"
2.5cm
8
30.00"
76cm
1.75"
4cm
R
D
J
Front Of Unit
Typical Mechanical Access (Plan View)
All F15 Models
Plumbing
Self-contained models are standard with a condensate
evaporator. If your unit does not have a condensate evap o ra tor,
or the evaporator fails, the unit's drain must have an outlet to an
appropriate drainage area or container.
Moisture collecting from improper drainage can
create a slippery surface on the floor and a hazard
to employees. It is the owner's responsibility to
CAUTION
provide a container or outlet for drainage.
Electrical connection
Refer to the amperage data on the specification pages, the serial
tag, your local code or the National Electrical Code to be sure the
unit is connected to the proper power source. A protected circuit
of the correct voltage and amperage must be run for con nec tion
of the line cord, or permanent connection to the unit.
Self-contained units have an ON/OFF switch located directly
behind the louvered panel covering the compressor section.
Simply turn the switch to ON to begin operation.
The power switch should be turned to OFF and
the unit disconnected from the power source
whenever performing service or maintenance
functions.
3.75"
10cm
C
3.75"
10cm
J= Junction Box
R= Refrigeration Lines,
0.25" Liquid,
0.37" Suction
D= 0.50" I.D. Drain