SCADA INTERFACE INSTRUCTIONS - OPTION 21Q - FOR A36D/TPSD SYSTEMS with 500 and 550 option.
A36D/TPSD
Modbus TCP
SCADA INTERFACE
OPTION 21Q
INSTRUCTIONS
This manual is valid for A36D/TPSD Chargers equipped with 341S control cards with
P341S0012 or P341S0013 software and 383S Communications Board
ECN/DATE
CPN 135484
21183-7 11/17
21183-2 12/16
106 BRADROCK DRIVE
DES PLAINES, IL. 60018-1967
(847) 299-1188
FAX: (847) 299-3061
ISSUE DATE: ECN 21183-7 11/2017
INSTRUCTION DRAWING NUMBER:
LOPT21Q-A36D-TPSD-1-341S
P25-

Advertisement

loading

Summary of Contents for La Marche A36D

  • Page 1 SCADA INTERFACE INSTRUCTIONS - OPTION 21Q - FOR A36D/TPSD SYSTEMS with 500 and 550 option. A36D/TPSD Modbus TCP SCADA INTERFACE OPTION 21Q INSTRUCTIONS This manual is valid for A36D/TPSD Chargers equipped with 341S control cards with P341S0012 or P341S0013 software and 383S Communications Board...
  • Page 2: Default Settings

    SCADA INTERFACE INSTRUCTIONS - OPTION 21Q - FOR A36D/TPSD SYSTEMS/341S Default Settings The LaMarche Communications Card is shipped with the following default settings; Port: RS232 Baud Rate: 9600 Data Bits: 8 Stop Bits: 1 Parity: None Board Configuration The communications card may be configured for RS232, RS485 or TCP communications.
  • Page 3 SCADA INTERFACE INSTRUCTIONS - OPTION 21Q - FOR A36D/TPSD SYSTEMS/341S RS232 & RS485 Serial Applications To configure the card for Serial applications you need to configure the board’s dipswitches and set the Address, Baud Rate and Parity as required in the customer calibration mode.
  • Page 4 SCADA INTERFACE INSTRUCTIONS - OPTION 21Q - FOR A36D/TPSD SYSTEMS/341S To assign the desire IP settings press the Assign IP button on the Toolbar. This will bring up the following screen: The Device Identification is located on the device itself as described in the dialog text above. An example of the Lantronix device is pictured below.
  • Page 5 SCADA INTERFACE INSTRUCTIONS - OPTION 21Q - FOR A36D/TPSD SYSTEMS/341S This dialog presents a choice between assigning an IP dynamically which would allow the device to operate on a network with a DHCP server however it is recommended that a specific IP address be assigned so it can be referenced directly on a SCADA Network.
  • Page 6 SCADA INTERFACE INSTRUCTIONS - OPTION 21Q - FOR A36D/TPSD SYSTEMS/341S Pressing Assign will start the process of programming the device to the new IP Settings. A progress bar and Status will appear indicating a successful operation as shown below: Pressing Finish will complete the IP setting change process. The DeviceInstaller Application can now be closed.
  • Page 7 Include AC Alarm in Summary Alarm (INCLUDED=1) Include Ground Detection Alarms in Summary Alarm (INCLUDED=1). TPSD ONLY. 00005 For A36D this point will always read 0 and writes to are prohibited. 00006 Include Over Temperature Alarm in Summary (INCLUDED=1) 00007...
  • Page 8 00024 Test Summary Alarm Contacts (BEGIN TEST=1, END TEST=0). 00025 Test Low Current Alarm Contacts (BEGIN TEST=1, END TEST=0). 00026 Test Open DC Protection Alarm Contacts (BEGIN TEST=1, END TEST=0). A36D ONLY. 02 - Discrete Inputs Address Name/Description 10000 AC Alarm Indicator (FAILURE=1)
  • Page 9 40018 AC Alarm Delay, Seconds, (1 to 300) None Ground Detection Alarm Delay, Seconds, (1-300) TPSD 40019 ONLY. For A36D this point will always read 0 and writes to are None prohibited. 40020 End of Discharge Alarm Delay, Seconds (1-300)
  • Page 10 SCADA INTERFACE INSTRUCTIONS - OPTION 21Q - FOR A36D/TPSD SYSTEMS/341S 04 - Input Registers Address Description, Units Scale Factor Local Temperature Probe Reading, Degrees C Note: A shorted probe will give a reading of –273 and an open 30009 None...