SCADA INTERFACE INSTRUCTIONS - OPTION 21Q - FOR A36D/TPSD SYSTEMS/341S
01 - Coils
Address
00021
Test Low Voltage Alarm Contacts (BEGIN TEST=1, END TEST=0).
00022
Test Positive Ground Contacts (BEGIN TEST=1, END TEST=0). TPSD ONLY.
00023
Test AC Alarm Contacts (BEGIN TEST=1, END TEST=0).
00024
Test Summary Alarm Contacts (BEGIN TEST=1, END TEST=0).
00025
Test Low Current Alarm Contacts (BEGIN TEST=1, END TEST=0).
00026
Test Open DC Protection Alarm Contacts (BEGIN TEST=1, END TEST=0). A36D ONLY.
02 - Discrete Inputs
Address
10000
AC Alarm Indicator (FAILURE=1)
10001
High Voltage Alarm Indicator (FAILURE=1)
10002
High Voltage Shutdown Alarm Indicator (FAILURE=1)
10003
Low Current Alarm Indicator (FAILURE=1)
Open DC Protection Alarm Indicator (FAILURE=1) A36D ONLY.
10004
For TPSD this point will always read 0.
Positive Ground Alarm Indicator (FAILURE=1). TPSD ONLY.
10005
For A36D this point will always read 0.
Negative Ground Alarm Indicator (FAILURE=1). TPSD ONLY.
10006
For A36D this point will always read 0.
10007
Summary Alarm Indicator (FAILURE=1)
10008
End of Discharge Alarm Indicator (FAILURE=1).
10009
Overload Alarm Indicator (FAILURE=1)
10010
Over Temperature Alarm Enable (ENABLED=1)
10011
Over Temperature Alarm Status (FAILURE=1)
Charger in Settings Menu (Set to 1 when charger is manually put into the settings menu
10012
through the front panel) Remote setting changes are disabled when this is set to 1 until
the local operator exits the Settings Menu.
SCADA Read Only Mode (ENABLED=1). Setting changes are not allowed when the
10013
charger is in the settings menu or when the SCADA Read Only Mode has been selected.
10014
Negative Ground Alarm Relay Contacts (CLOSED=1, OPEN=0). TPSD ONLY.
10015
High Voltage Alarm Relay Contacts (CLOSED=1, OPEN=0).
10016
Low Voltage Alarm Relay Contacts (CLOSED=1, OPEN=0).
10017
Positive Ground Alarm Relay Contacts (CLOSED=1, OPEN=0). TPSD ONLY.
10018
AC Fail Alarm Relay Contacts (CLOSED=1, OPEN=0).
10019
Summary Alarm Relay Contacts (CLOSED=1, OPEN=0).
10020
Low Current Alarm Relay Contacts (CLOSED=1, OPEN=0).
10021
Open DC Protection Alarm Relay Contacts (CLOSED=1, OPEN=0).
Page 8 of 10