SCADA INTERFACE INSTRUCTIONS - OPTION 21Q - FOR A36D/TPSD SYSTEMS/341S
04 - Input Registers
Address
Local Temperature Probe Reading, Degrees C
Note: A shorted probe will give a reading of –273 and an open
30009
probe will give a reading of+273
Temperature Probe Status
30010
OK=0,SHORTED=1,OPEN=2,HARDWARE FAILURE=3
30011
Maximum Settable Alarm Voltage, MAXAV, Volts
30012
Maximum Settable Alarm Current, MAXAI, Amps
Over Temperature Probe Reading, Degrees C
Note: A shorted probe will give a reading of –273 and an open
30013
probe will give a reading of+273
Over Temperature Probe Status
30014
OK=0,SHORTED=1,OPEN=2,HARDWARE FAILURE=3
30015
Charger Series. (0=TPSD,1=A36D)
Battery Voltage, Volts
30016
Note: This point should only be monitored when DI 10015=1
NOT AVAILABLE= 30000, FAILED = 30001
Aux Temperature Probe #1, C
30017
Note: NOT AVAILABLE=30000, SHORTED=30001,
OPEN=30002, FAILED=30003
Aux Temperature Probe #2, C
30018
Note: NOT AVAILABLE=30000, SHORTED=30001,
OPEN=30002, FAILED=30003
Low Voltage Alarm Status (0=NO ALARM,1=LOW VOLTAGE
30019
ALARM,2=LOW BATTERY VOLTAGE ALARM)
P60-407S Board Failure Alarm (0=N/A,1=NO ALARM,2-
30020
ALARM)
Page 10 of 10
Description, Units
Scale Factor
None
None
0.1
0.1
None
None
None
0.1
None
None
None
None