Specification
Control Modules: 2 x Control module locations
Cable Entry: Supply/Control
Compliance: DMC2-UL: UL, CSA, CE, RCM, FCC, ICES-003
Operating Environment: 0°C to 40°C (32°F to 104°F) ambient temperature
Shipping and Storage: -25°C to 60°C (-13°F to 140°F) ambient temperature
Construction: Galvanized Steel case with powder coated front covers
Dimensions: H: 540mm (21.3")
Federal Communications Commission (FCC) Compliance Notice: Radio Frequency Notice
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses, and can radiate
radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications.
However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or
television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or
more of the following measures:
Reorient or relocate the receiving antenna.
Increase the separation between the equipment and receiver.
Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
Consult the dealer or an experienced radio/TV technician for help.
CAUTION: Any modifications not approved by the manufacturer of this device could void the user's authority to operate this device.
Compliance to Industry Canada ICES-003: CAN ICES-3(B)/NMB-3(B)
Dynalite manufactured by WMGD Pty Ltd (ABN 33 097 246 921) Unit 6, 691 Gardeners Road Mascot NSW 2020 Australia Tel: +61 2 8338 9899 Fax: +61 2 8338 9333
E-Mail: support.controls@philips.com
8
DMC2 Installation Instructions Rev 03
Top:
Side:
Back:
Data
Side:
Bottom:
Note:
28.2mm (1.1") opening is suitable for 3/4" conduit
22.2mm (0.87") opening is suitable for 1/2" conduit
Overvoltage category III, Pollution Degree II
DMC2-CE: CE, RCM, Overvoltage category III, Pollution Degree II
NOTE:
The temperature limits and current-carrying capacities of the communication
wires specified in HD 384.5.523 shall not be exceeded.
Installation of home and building automation control shall comply with HD 60364-
4-41.
Network Topology for installation is Daisy Chain.
Input: Voltage rating:
Current rating:
0% to 90% RH non-condensing
0% to 90% RH non-condensing
W: 380mm (15")
D: 106mm (4.2")
Weight: 7.71 kg (17 lbs) (excluding all modules)
DMC2 Installation Instructions Rev 03 Specifications subject to change without notice
4 x 28.2mm (1.1")
2 x 22.2mm (0.87")
7 x 28.2 (1.1")
7 x 22.2mm (0.87")
4 x 28.2mm (1.1")
3 x 22.2mm (0.87")
1 x 28.2mm (1.1")
1 x 28.2mm (1.1")
120/230/277 VAC +10% / -15%
50/60 Hz 3-Phase, 4-Wire (Y), or Single Phase
32 A per phase for 3-phase supply, or single phase 63 A max