Neptronic RM020FN Specification And Installation Instructions

Advertisement

Quick Links

Technical Data
Auxiliary switches
Fail safe - Enerdrive
Power consumption
Torque
Power supply
Running time through 90º
Feedback
Electrical connection
Inlet bushing
Control signal
Angle of rotation
Direction of rotation
Operating temperature
Storage temperature
Relative Humidity
Weight
Warning: Do not press the clutch when actuator is powered
Dimensions
Caution
We strongly recommend that all Neptronic
prevent interference with, and/or possible damage to incompatible equipment.
When multiple actuators are wired on a single transformer, polarity must be observed. Long wiring runs create voltage drop which may affect the actuator performance.
1
Enerdrive System U.S.A. Patent #5,278,454
TMFN-RMFN_120124.docx
Features
TM000FN
TM020FN
No
Yes (2)
No
25 VA
120 in.lb. [13.5 Nm] at rated voltage
Analog, Digital or PWM programmable (factory set with analog control signal)
0 to 90 degrees, electronically adjustable (factory set with 90º stroke)
Reversible, Clockwise (CW) or Counterclockwise (CCW) (factory set with CW direction)
4.5 lbs. [2 kg]
®
products be wired to a separate transformer and that transformer shall service only Neptronic
Specification & Installation Instructions
:
Clutch for manual adjustments.
Maintenance free.
Position indicator.
Control signal fully programmable.
Brushless DC driven motor.
Fail safe by Enerdrive System
(on model 060 & 080).
Auxiliary switches
(on model 020 & 080).
TM060FN
TM080FN
RM000FN
No
Yes (2)
Yes
40 VA Peak, 25 VA
22 to 26 VAC or 28 to 32 Vdc
15 to 20 sec torque dependant
4 to 20 mA or 2 to 10 Vdc adjustable
18 AWG [0.8 mm
2 inlet bushing of 7/8 in [22.2 mm]
0ºF to 122ºF [-18º C to 50ºC]
-22ºF to 122ºF [-30º C to 50ºC]
5 to 95 % non condensing.
Dimension
1
RM020FN
RM060FN
No
Yes (2)
No
25 VA
240 in.lb. [27 Nm] at rated voltage
2
] minimum
7 lbs. [3.2 kg]
Imperial (in)
A
5.20
B
1.33
C
9.13
D
3.55
®
products. This precaution will
Actuator
TM000FN
TM020FN
TM060FN
TM080FN
RM000FN
RM020FN
RM060FN
RM080FN
RM080FN
No
Yes (2)
Yes
40 VA Peak, 25 VA
Metric (mm)
132.1
33.8
231.9
90.2
1

Advertisement

loading

Summary of Contents for Neptronic RM020FN

  • Page 1 ® ® We strongly recommend that all Neptronic products be wired to a separate transformer and that transformer shall service only Neptronic products. This precaution will prevent interference with, and/or possible damage to incompatible equipment. When multiple actuators are wired on a single transformer, polarity must be observed. Long wiring runs create voltage drop which may affect the actuator performance.
  • Page 2 TM000/020/060/080FN RM000/020/060/080FN Specification & Installation Instruction Mechanical Installation Manually close the damper blades and positioned the actuator at 0º or 90º. Slide the actuator onto the shaft. Tighten the nuts on the “U” bolt to the shaft with a 10mm wrench to a torque of 150 in.lb.
  • Page 3 TM000/020/060/080FN RM000/020/060/080FN Specification & Installation Instruction PC Board Dip switch settings Input in mA Feedback in Vdc Fail safe return at 90º Potentiometer Rotation: CCW Pins for PWM selection Clutch Microcontroller Rotation: CW Reset button Terminal Fail safe return at 0º Input in Vdc Feedback in mA 1 2 3 4...
  • Page 4 TM000/020/060/080FN RM000/020/060/080FN Specification & Installation Instruction Zero and span calibration This feature is applicable to analog control signal only. Remove power and put all dip switches "OFF". (factory preset). Apply power and, within 10 seconds press and hold the reset button until the LED blinks once. The Zero and span calibration process then start.

This manual is also suitable for:

Rm060fnRm080fnRm000fnTm000fnTm020fnTm060fn ... Show all