Siemens AE-30U Operation And Installation Instructions page 2

Alarm extender module

Advertisement

NOTES:
1. When emergency power is provided using
charger/ transfer module, Model BC-35, 24 VDC
notification appliances must be used with EOL
device, Model EL-31. When BC-35 is not used,
120 VAC notification appliances may be
employed by use of AC program plug, Model
JP-A, in P2 of CP-35 and Model EL-32 EOL
device, or by use of 24 VDC notification
appliances with DC program plug, Model
JP-D, in P2 and Model EL-31 EOL device.
2. Notification appliance circuits may be
activated from the silenceable system alarm
P/N 315-085099-16
STYLE Y (CLASS B)
CONNECTED
POLARIZED
NOTIFICATION
APPLIANCES
POLARITY SHOWN IN
SUPERVISORY CONDITION:
SUPV
24 VDC, 5mA
ALARM 24 VDC or 120 VAC,
1.5A MAX
CP-35
INPUT POWER
(SEE NOTE 1)
3 OHMS MAX TOTAL LINE
RESISTANCE OF NOTIFICATION
APPLIANCE CIRCUIT
CONNECTING WIRES
NOTE:
Refer to the BI-35 Installation
Instructions, P/N 315-086257,
for detailed wiring information
when using the AE-30U in
conjunction with the BI-35
module.
CP-35
(SEE NOTE 2)
ACTUATION
INPUT
POLARIZED NOTIFICATION
APPLIANCES (SEE NOTE 3)
END OF LINE DEVICE
(SEE NOTE 1)
output signal, terminal 36 of CP-35, or from the
non-silenceable system alarm output signal,
terminal 42 of CP-35. When other alarm signals
such as coding or time delay/limit are required,
see individual module connection diagrams.
3. Use only the compatible polarized notification
appliances listed in P/N 315-096363.
4. To use power limited wiring to NFPA 70, NEC
Article 760, the notification appliance circuits
(terminals 3 and 4) must use the PLM-35
module. Refer to Instructions P/N 315-093495.