24
Feeder Terminal
Operation accuracy
Start time
Reset time
Reset ratio, typically
Retardation time
Operate time accuracy at DT mode
Directional earth-fault protection, low-set stage, DEF2Low, Io> (67N-1)
Start current
Start voltage
Operate time at DT mode
Time multiplier at IDMT mode
Operation mode
Operation criteria
Operation direction
Basic angle 
b
Operation characteristic
Intermittent E/F
Measuring mode
Drop-off time of the operate time counter
Operation accuracy
Start time
Reset time
Reset ratio, typically
Retardation time
Operate time accuracy at DT mode
Accuracy class index E at IDMT mode
REF 541, REF 543, REF 545.
Note! The values below apply when f/fn = 0.95...1.05
±2.5% of set value or + 0.01 x In
Injected currents > 2.0 x start current:
internal time < 32 ms
total time < 40 ms
40...1000 ms (depends on the minimum pulse width set for
the trip output)
0.95
< 45 ms
±2% of set value or ±20 ms
1.0...500.0% of In
2.0...100.0% of Un
0.1...300.0 s
0.05...1.00
Not in use
Definite time
Extremely inverse
Very inverse
Normal inverse
Long time inverse
Basic angle & Uo
Basic angle
IoSin/Cos & Uo
IoSin/Cos
Non-directional Io
Non-directional Uo
Forward
Reverse
-90... 60
IoSin()
IoCos()
Not active
Active
Peak-to-peak
Fundamental frequency
0...1000 ms
Note! The values below apply when f/fn = 0.95...1.05
±2.5% of set value + 0.0005 x In
±2.5% of set value or + 0.01 x Un
Phase angle ±2
Injected neutral current > 2.0 x start current and
residual voltage > 2.0 x start voltage:
internal time < 72 ms
total time < 80 ms
40...1000 ms (depends on the minimum pulse width set for
the trip output)
0.95
< 50 ms
±2% of set value or ±20 ms
Class index E = 5.0 or ±20 ms
1MRS750443-MBG