ABB REF 541 Product Manual page 23

Feeder terminal
Hide thumbs Also See for REF 541:
Table of Contents

Advertisement

Feeder Terminal
Operation accuracy
Start time
Reset time
Reset ratio, typically
Retardation time
Operate time accuracy at DT mode
Non-directional earth-fault protection, low-set stage, NEF1Low, Io> (51N-1)
Start current
Operate time at DT mode
Time multiplier at IDMT mode
Operation mode
Measuring mode
Drop-off time of the operate time counter
Operation accuracy
Start time
Reset time
Reset ratio, typically
Retardation time
Operate time accuracy at DT mode
Accuracy class index E at IDMT mode
Non-directional earth-fault protection, high-set stage, NEF1High, Io>> (51N-2), and instantaneous
stage, NEF1Inst, Io>>> (51N-3)
Start current
Operate time
Operation mode
Measuring mode
Drop-off time of the operate time counter
REF 541, REF 543, REF 545.
Note! The values below apply when f/fn = 0.95...1.05
0.1...10 x In: ±2.5% of set value or ±0.01 x In
10...40 x In: ±5.0% of set value
±2.5% of measured voltage or ±0.01 x Un
±2
Injected currents > 2.0 x start current:
internal time < 42 ms
total time < 50 ms
40...1000 ms (depends on the minimum pulse width set for
the trip output)
0.95
< 45 ms
±2% of set value or ±20 ms
1.0...500.0% of In
0.05...300.00 s
0.05...1.00
Not in use
Definite time
Extremely inverse
Very inverse
Normal inverse
Long time inverse
RI-type inverse
RD-type inverse
IEEE Extremely inverse
IEEE Very inverse
IEEE Short time inverse
IEEE Short time extremely inverse
IEEE Long time extremely inverse
IEEE Long time very inverse
IEEE Long time inverse
Peak-to-peak
Fundamental frequency
0...1000 ms
Note! The values below apply when f/fn = 0.95...1.05
±2.5% of set value + 0.0005 x In
Injected currents > 2.0 x start current:
internal time < 32 ms
total time < 40 ms
40...1000 ms (depends on the minimum pulse width set for
the trip output)
0.95
< 45 ms
±2% of set value or ±20 ms
Class index E = 5.0 or ±20 ms
0.10...12.00 x In
0.05...300.00 s
Not in use
Definite time
Instantaneous
Peak-to-peak
Fundamental frequency
0...1000 ms
1MRS750443-MBG
23

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ref 543Ref 545

Table of Contents