ABB REF 541 Product Manual page 19

Feeder terminal
Hide thumbs Also See for REF 541:
Table of Contents

Advertisement

Feeder Terminal
Analogue output on RTD/analogue module, MEAO1...4 (AO1...AO4)
The analogue output function blocks handle the scaling of any internal REAL type IEC 61131-3 based
signal to fit a selectable 0...20 mA or 4...20 mA range for use with the outputs on the RTD/analogue
module.
General REAL type input
The recording can be triggered by any (or several) of the alternatives listed below:
triggering on the rising or falling edge of any (or several) of the digital inputs
triggering on overcurrent, overvoltage or undervoltage
manual triggering via the menu or with the push-button F on the front panel (if configured)
triggering via serial communication
periodic triggering
The recording length depends on the number of recordings and inputs used. For example, the following
combination of recording length, number of recordings and number of inputs is available at 50 Hz:
 recordings \  inputs
1
1
1163 cyc.
23.2 s
5
232 cyc.
4.6 s
10
115 cyc.
2.3 s
System frequency measurement, MEFR1 (f)
Frequency
Average Freq.
Voltage U
Three-phase power and energy measurement, MEPE7 (PQE)
P3 (kW)
Q3 (kvar)
Power factor DPF
Power factor PF
P3 demand (kW)
Q3 demand (kvar)
Energy kWh
Reverse kWh
Energy kvarh
Reverse kvarh
Residual voltage measurement, MEVO1A and MEVO1B (Uo, Uo_B)
Uo
Uo
Three-phase voltage measurement, MEVO3A and MEVO3B (3U, 3U_B)
UL1_U12
UL2_U23
UL3_U31
UL1_U12
UL2_U23
UL3_U31
UL1_U12 average
UL2_U23 average
UL3_U31 average
UL1_U12 average
UL2_U23 average
UL3_U31 average
REF 541, REF 543, REF 545.
-10000.00000...10000.00000
3
10
412 cyc.
126 cyc.
8.2 s
2.5 s
82 cyc.
25 cyc.
1.6 s
0.5 s
41 cyc.
12 cyc.
0.8 s
0.24 s
10.00...75.00 Hz
10.00...75.00 Hz
0.0...2.0 x Un
-999999...999999 kW
-999999...999999 kvar
-1.00...1.00
-1.00...1.00
-999999...999999 kW
-999999...999999 kvar
0...999999999 kWh
0...999999999 kWh
0...999999999 kvarh
0...999999999 kvarh
0...150000 V
0.0...120.0% Un
0.00...999.99 kV
0.00...999.99 kV
0.00...999.99 kV
0.00...2.00 x Un
0.00...2.00 x Un
0.00...2.00 x Un
0.00...999.99 kV
0.00...999.99 kV
0.00...999.99 kV
0.00...2.00 x Un
0.00...2.00 x Un
0.00...2.00 x Un
1MRS750443-MBG
19

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ref 543Ref 545

Table of Contents