PROGRAMMING CEILING OCCUPANCY SENSOR

Ceiling Occupancy Sensor programming is the same for both single, multiple and all sensors
on the network. Programming selections will affect all illuminated sensors.

Mode

The MODE field allows access to intelligence level, Automatic or Manual On, and reset to
factory default.
The Occupancy Sensor time-off delay can operate in four different modes. The default is
Fixed Time Mode, which means the fixed time delay (as set by the user) is always used. The
other three modes allow the sensor to automatically adjust to the space and occupancy
patterns, differing in how aggressive the sensor is with saving energy. Conservative Mode will
automatically adjust the time-off between 5 to 30 minutes. Normal Mode will automatically
adjust the time-off between 3 and 15 minutes for enhanced energy savings. Aggressive Mode
will automatically adjust the time-off delay between 1 minute and 3 minutes for maximum
energy savings.
The Occupancy Sensor can be configured to operate in either a Manual On or Automatic On
Mode. In Manual On Mode, the lights will only turn on when a designated switch activates the
relay. The lights will turn off automatically when vacancy is detected for the time delay
period. In the Automatic On Mode, the lights will automatically turn on as soon as occupancy
is detected. The lights will turn off when either the designated switch deactivates the relay or
automatically when vacancy is detected for the time delay
To change the mode of the sensor:
Step 1. Enter Programming Mode (refer to page 6.)
Step 2. Press MODE button.
Step 3. Select intelligence level:
Button 1
Button 2
Button 3
Button 4
Step 4. Select activation mode:
Button 5
Button 6
Button 7
Button 8
Button 0
Exit programming by pressing the PGM (Program) button or continue with programming by
selecting another field.
Aggressive Intelligence
Normal Intelligence
Conservative Intelligence
Fixed Timing
Manual ON
Automatic ON
Factory Default Manual ON
Factory Default Automatic ON
Factory Default
Installation & Operation Guide
* Factory Default
* Factory Default
Press and hold for 3 or more sec-
onds to factory default all settings.
* Fixed Timing & Automatic
7