Advanced Configuration/Optimization - Daikin Altherma 08CA Installer's Reference Manual

Hybrid heat pump
Table of Contents

Advertisement

INFORMATION
When leaving water temperature modulation is enabled,
the weather‑dependent curve needs to be set to a higher
position than [8-06] plus the minimum leaving water
temperature setpoint required to reach a stable condition
on the comfort setpoint for the room. To increase
efficiency, modulation can lower the leaving water setpoint.
By setting the weather‑dependent curve to a higher
position, it cannot drop below the minimum setpoint. Refer
to the illustration below.
T t
+[8-06]
−[8-06]
a
Weather-dependent curve
b
Minimum leaving water temperature setpoint required to
reach a stable condition on the comfort setpoint for the
room.
Leaving water temperature: Emitter type
Only applicable in case of room thermostat control. Depending on
the system water volume and the heat emitters type, the heat up or
cool down of a space can take longer. This setting can compensate
for a slow or a quick heating/cooling system during the heat up/cool
down cycle.
Note: The setting of the emitter type will influence the maximum
modulation of the desired leaving water temperature and the
possibility for usage of the automatic cooling/heating changeover
based on the indoor ambient temperature.
Therefore it is important to set this correctly.
#
Code
[A.3.1.1.7]
[9‑0B]
Emitter type:
Reaction time of the system:
▪ Quick
water volume, fan coils, or radiators.
▪ Slow Example: Large water volume,
floor heating loops.
Quick heat up function
Only applicable in case of room thermostat control. The function will
start up the gas boiler when the actual room temperature is 3°C
lower than the desired room temperature. The large boiler capacity
can boost up the room temperature quickly to the desired
temperature. This can be useful after a long period of absence or
after a break-down of the system. During the quick heat up function,
the setpoint of the gas boiler will be the maximum heating setpoint:
[9‑00].
#
Code
N/A
[C‑0A]
Indoor quick heat up function
▪ 0 (default): OFF.
▪ 1: On.
Domestic hot water control
Only applicable in case an optional domestic hot water tank is
installed.
This is always applicable for Switzerland.
EVLQ05+08CAV3 + EHYHBH05AA + EHYHBH/X08AA +
EHYKOMB33AA
Daikin Altherma hybrid heat pump
4P355634-1C – 2018.06
a
b
T a
Description
(default)
Example:
Small
Description
Configuring the desired tank temperature
The domestic hot water can be prepared in 3 different ways. They
differ from each other by the way the desired tank temperature is set
and how the unit acts upon it.
#
Code
[A.4.1]
[6-0D]
Domestic hot water Type:
▪ 0 (Reheat only): Only reheat operation
is allowed.
▪ 1 (Reheat + sched.): The domestic hot
water tank is heated according to a
schedule and between the scheduled
heatup cycles, reheat operation is
allowed.
▪ 2
domestic hot water tank can ONLY be
heated according to a schedule.
See
"Domestic hot water control: advanced"  on page  70
details.
INFORMATION
If a third‑party tank is present in the system ([E‑07]=6), it is
recommended to set [6‑0D] to "0" (i.e. Reheat only).
Maximum DHW temperature setpoint
The maximum temperature that users can select for the domestic
hot water. You can use this setting to limit the temperatures at the
hot water taps.
INFORMATION
During disinfection of the domestic hot water tank, the
DHW temperature can exceed this maximum temperature.
INFORMATION
Limit the maximum hot water temperature according to the
applicable legislation.
#
Code
[A.4.5]
[6‑0E]
Maximum setpoint
The maximum temperature that users
can select for the domestic hot water.
You can use this setting to limit the
temperature at the hot water taps.
The maximum temperature is NOT
applicable during disinfection function.
See disinfection function.
In case of [E‑06]=1 (tank installed):
▪ [E‑07]≠6: 40~75°C (default: 75°C)
▪ [E‑07]=6: 40~60°C (default: 60°C)
In case of [E‑06]=0 (no tank installed):
▪ 40~65°C (default: 65°C)
Contact/helpdesk number
#
Code
[6.3.2]
N/A
Number that users can call in case of
problems.
8.1.3

Advanced configuration/optimization

Space heating/cooling operation: advanced
Preset leaving water temperature
You can define preset leaving water temperatures:
8 Configuration
Description
(Scheduled
only)(default):
The
for more
Description
Description