Daikin Altherma 08CA Installer's Reference Manual page 61

Hybrid heat pump
Table of Contents

Advertisement

#
Code
[A.2.2.C]
[D‑0A]
Optional gas meter:
▪ 0 (No)(default): NOT installed
▪ 1: Installed (1 pulse/m³)
▪ 2: Installed (10 pulse/m³)
▪ 3: Installed (100 pulse/m³)
Savings mode
The user can choose whether switching between operation modes is
either economically or ecologically optimised. Set to Economical, the
system will in all operating conditions select the energy source (gas
or electricity) based on energy prices, resulting in a minimisation of
energy costs. Set to Ecological, the heat source will be selected
based on ecological parameters, resulting in a minimisation of
primary energy consumption.
#
Code
[A.6.7]
[7‑04]
Defines whether switching between
operation modes is either economically
or ecologically optimised.
▪ 0 (Economical)(default): reduction of
energy costs
▪ 1 (Ecological): reduction of primary
energy
necessarily energy costs
Primary energy factor
The primary energy factor indicates how many units of primary
energy (natural gas, crude oil, or other fossil fuels, prior to
undergoing any human-made conversions or transformations) are
needed to obtain 1 unit of a certain (secondary) energy source, such
as electricity. The primary energy factor for natural gas is 1.
Assuming an average electricity production efficiency (including
transportation losses) of 40%, the primary energy factor for
electricity equals 2.5 (=1/0.40). The primary energy factor allows you
to compare 2 different energy sources. In this case, the primary
energy use of the heat pump is compared to the natural gas use of
the gas boiler.
#
Code
N/A
[7‑03]
Compares the primary energy use of the
heat pump with that of the boiler.
Range: 0~6, step: 0.1 (default: 2.5)
INFORMATION
▪ The primary energy factor can always be set, but is
only used in case the savings mode is set to
Ecological.
▪ To set electricity price values, do NOT use overview
settings. Set them in the menu structure instead
([7.4.5.1], [7.4.5.2], and [7.4.5.3]). For more information
on how to set the energy prices, see the operation
manual and the user reference guide.
Space heating/cooling control
The basic required settings in order to configure the space heating/
cooling of your system are described in this chapter. The weather-
dependent installer settings define the parameters for the weather-
dependent operation of the unit. When weather-dependent operation
is active, the water temperature is determined automatically
depending on the outdoor temperature. Low outdoor temperatures
will result in warmer water and vice versa. During weather-
dependent operation, the user has the possibility to shift up or down
the target water temperature by a maximum of 10°C.
See the user reference guide and/or operation manual for more
details about this function.
EVLQ05+08CAV3 + EHYHBH05AA + EHYHBH/X08AA +
EHYKOMB33AA
Daikin Altherma hybrid heat pump
4P355634-1C – 2018.06
Description
Description
consumption,
but
not
Description
Leaving water temperature: Main zone
#
Code
[A.3.1.1.1]
N/A
LWT setpoint mode:
▪ Fixed: The desired leaving water
temperature is:
▪ NOT weather-dependent (i.e. does
▪ fixed in time (i.e., NOT scheduled)
▪ Weather dep. (default): The desired
leaving water temperature is:
▪ weather-dependent (i.e. depends
▪ fixed in time (i.e., NOT scheduled)
#
Code
[A.3.1.1.1]
N/A
<< continuation
▪ Fixed/scheduled: The desired leaving
water temperature is:
▪ NOT
▪ according
▪ WD/scheduled: The desired leaving
water temperature is:
▪ weather-dependent
▪ according
#
Code
[7.7.1.1]
[1‑00]
Set weather-dependent heating:
T t
[1‑01]
[1‑02]
[1-02]
[1‑03]
[1-03]
▪ T
(main)
▪ T
8 Configuration
Description
NOT
depend
on
the
outdoor
ambient temperature)
on
the
outdoor
ambient
temperature)
continued >>
Description
weather-dependent
does NOT depend on the outdoor
ambient temperature)
a
schedule.
scheduled
actions
consists
desired shift actions, either preset
or custom.
Remark: This value can only be
set in leaving water temperature
control.
(i.e.,
does
depend on the outdoor ambient
temperature)
a
schedule.
scheduled
actions
consists
desired
leaving
water
temperatures
either
preset
custom
Remark: This value can only be
set in leaving water temperature
control.
Description
[1-00]
[1-01]
: Target leaving water temperature
t
: Outdoor temperature
a
continued >>
Installer reference guide
(i.e.,
The
of
The
of
or
T a
61