4/8
Field settings table
Breadcrumb
Field code
Setting name
└─ Disinfection
A.4.4.1
[2-01]
Disinfection
A.4.4.2
[2-00]
Operation day
A.4.4.3
[2-02]
Start time
A.4.4.4
[2-03]
Temperature target
A.4.4.5
[2-04]
Duration
└─ Maximum setpoint
A.4.5
[6-0E]
└─ SP mode
A.4.6
└─ Weather dependent curve
A.4.7
[0-0B]
Weather-dependent curve
A.4.7
[0-0C]
Weather-dependent curve
A.4.7
[0-0D]
Weather-dependent curve
A.4.7
[0-0E]
Weather-dependent curve
└─ Heat sources
└─ Boiler
A.5.2.2
[5-01]
Equilibrium temp.
└─ System operation
└─ Auto restart
A.6.1
[3-00]
└─ Pwr consumpt. Control
A.6.3.1
[4-08]
Mode
A.6.3.2
[4-09]
Type
A.6.3.3
[5-05]
Amp. value
A.6.3.4
[5-09]
kW value
A.6.3.5.1
[5-05]
Amp. limits for DI
A.6.3.5.2
[5-06]
Amp. limits for DI
A.6.3.5.3
[5-07]
Amp. limits for DI
A.6.3.5.4
[5-08]
Amp. limits for DI
A.6.3.6.1
[5-09]
kW limits for DI
A.6.3.6.2
[5-0A]
kW limits for DI
A.6.3.6.3
[5-0B]
kW limits for DI
A.6.3.6.4
[5-0C]
kW limits for DI
└─ Averaging time
A.6.4
[1-0A]
└─ Ext amb. sensor offset
A.6.5
[2-0B]
└─ Savings mode
A.6.7
[7-04]
└─ Emergency
A.6.C
└─ Overview settings
A.8
[0-00]
Leaving water value for high ambient temp. for LWT add zone heating WD curve.
A.8
[0-01]
Leaving water value for low ambient temp. for LWT add zone heating WD curve.
A.8
[0-02]
High ambient temp. for LWT add zone heating WD curve.
A.8
[0-03]
Low ambient temp. for LWT add zone heating WD curve.
A.8
[0-04]
Leaving water value for high ambient temp. for LWT add zone cooling WD curve.
A.8
[0-05]
Leaving water value for low ambient temp. for LWT add zone cooling WD curve.
A.8
[0-06]
High ambient temp. for LWT add zone cooling WD curve.
A.8
[0-07]
Low ambient temp. for LWT add zone cooling WD curve.
A.8
[0-0B]
Leaving water value for high ambient temp. for DHW WD curve.
A.8
[0-0C]
Leaving water value for low ambient temp. for DHW WD curve.
4P353731-1E - 2017.02
DHW setpoint for high ambient temp. for DHW
WD curve.
DHW setpoint for low ambient temp. for DHW
WD curve.
High ambient temp. for DHW WD curve.
Low ambient temp. for DHW WD curve.
Limit DI1
Limit DI2
Limit DI3
Limit DI4
Limit DI1
Limit DI2
Limit DI3
Limit DI4
Range, step
Default value
R/W
0: No
1: Yes
R/W
0: Each day
1: Monday
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
7: Sunday
R/W
0~23 hour, step: 1 hour
23
R/W
fixed value
60°C
R/W
40~60 min, step: 5 min
40 min
R/W
[E-06]=1
[E-07] ≠
40~75°C, step: 1°C, 75°C
6:
[E-07] = 6: 40~60°C, step: 1°C, 60°C
[E-06]=0
40~65°C, step: 1°C, 65°C
R/W
0: Fixed
1: Weather dep.
R/W
35~[6-0E]°C, step: 1°C
55°C
R/W
45~[6-0E]°C, step: 1°C
60°C
R/W
10~25°C, step: 1°C
15°C
R/W
-40~5°C, step: 1°C
-10°C
R/W
-15~35°C, step: 1°C
5°C
R/W
0: No
1: Yes
R/W
0: No limitation
1: Continuous
2: Digital inputs
R/W
0: Current
1: Power
R/W
0~50 A, step: 1 A
50 A
R/W
0~20 kW, step: 0,5 kW
20 kW
R/W
0~50 A, step: 1 A
50 A
R/W
0~50 A, step: 1 A
50 A
R/W
0~50 A, step: 1 A
50 A
R/W
0~50 A, step: 1 A
50 A
R/W
0~20 kW, step: 0,5 kW
20 kW
R/W
0~20 kW, step: 0,5 kW
20 kW
R/W
0~20 kW, step: 0,5 kW
20 kW
R/W
0~20 kW, step: 0,5 kW
20 kW
R/W
0: No averaging
1: 12 hours
2: 24 hours
3: 48 hours
4: 72 hours
R/W
-5~5°C, step: 0,5°C
0°C
R/W
0: Economical
1: Ecological
R/W
0: Manual
1: Automatic
R/W
[9-05]~min(45,[9-06])°C, step: 1°C
35°C
R/W
[9-05]~[9-06]°C, step: 1°C
60°C
R/W
10~25°C, step: 1°C
15°C
R/W
-40~5°C, step: 1°C
-10°C
R/W
[9-07]~[9-08]°C, step: 1°C
8°C
R/W
[9-07]~[9-08]°C, step: 1°C
12°C
R/W
25~43°C, step: 1°C
35°C
R/W
10~25°C, step: 1°C
20°C
R/W
35~[6-0E]°C, step: 1°C
55°C
R/W
45~[6-0E]°C, step: 1°C
60°C
Installer setting at variance with
default value
Date
Value
*HYHBH/X*AAV3