Air Purge - Samsung APC3240C Owner's Instructions & Installation Manual

Split - type packaged air conditioner (cool)
Table of Contents

Advertisement

AIR PURGE

The air in the indoor unit and in the pipe must be purged. If air remains in the refrigeration pipes, it will affect the
compressor, reduce to cooling capacity and could lead to a malfunction.
Use Vacuum Pump as shown at the figure.
1. Connect each assembly pipe to the appropriate valve on the outdoor unit and tighten the flare nut.
2. Connect the charging hose of low pressure side of manifold gauge to the packed valve having a service port as
shown at the figure.
3. Open the valve of the low pressure side of manifold gauge counter-clockwise.
4. Purge the air from the system using vacuum pump for about 10 minutes.
- Close the valve of the low pressure side of manifold gauge clockwise.
- Make sure that pressure gauge show -0.1MPa(-76cmHg) after about 10 minutes.
This procedure is very important in order to avoid gas leak.
- Turn off the vacuum pump.
- Remove the hose of the low pressure side of manifold gauge.
5. Set valve cork of both liquid side and gas side of packed valve to the open position.
6. Mount the valve stem nuts and the service port cap to the valve, and tighten them at the torque of 18N•m with
a torque wrench.
7. Check for gas leakage.
- At this time, especially check for gas leakage from the 3-way valve's stem nuts, and from the service port cap.
OUTDOOR UNIT
Gas side
Liquid side
B
32
E-
A
Flare nut
Valve cock
Cap
Needle valve cap
D
Liquid side
Vacuum
3-way
Pump
valve
B
Indoor unit
C
Gas side
3-way
valve
A
Outdoor unit

Advertisement

Table of Contents
loading

This manual is also suitable for:

Upc3240c

Table of Contents