Area Depth Angle Adjustments
Depth angle adjustment
screw for the Presence/
Motion area.
-2
0
-6
Shallow
+4
-10
+8
The Presence/Motion area angle depth
adjustment screw adjusts rows 1-5
simultaneously.
Sensitivity Adjustment
Presence/Motion
Approach sensitivity
sensitivity
Low
High
Use the area adjustment tool to change sensitivity.
Cover Installation
The cover locking tab on the sensor must align with
the locking catch on the sensor cover.
Troubleshooting
Operation indicator table
Operation Indicator color
Status
Stand-by (installation mode)
Yellow
Stand-by (operation mode)
Green
BLUEZONE (1st row) detection
Blue
2nd row detection
Red blinking
3rd-4th row detection
Red
5th row detection
Orange
Approach (6th row) detection
Orange blinking
Signal saturation
Slow green blinking
Sensor failure
Fast green blinking
(Continued from other side)
Deep
The Approach area angle depth
adjustment screw adjusts row 6
independently.
The Presence/Motion sensitivity potentiometer is used to adjust the detec-
tion area sensitivity for rows 1-5. The Approach sensitivity potentiometer is
used to adjust the detection area sensitivity of row 6. Turning clockwise in-
creases the sensitivity; turning counterclockwise decreases the sensitivity.
1sec
18730 Wilmington Ave, Unit 100
Rancho Dominguez, CA 90220
Ph 310 214-8644
Fax 310 898-1098
Toll free 800 877-6656
www.ot-inc.com
Depth angle adjustment
screw for the Approach
area.
Deep
Shallow
-5
0
-10
-15
+10
Push cover straight into the locking tab on the sensor.
Operation LED turns FLASHING RED, then the door reopens
(Row 2 Presence Detection Door).
Adjust Presence/Motion adjustment screw Clockwise until ghost-
ing stops.
Note: Before making adjustments set dipswitch 18 ON, once
adjustment are complete set dipswitch 18 Off.
Note: Walk Test
Perform walk test procedure to verify substantial compliance with
ANSI/BHMA A156.10 section 8.
OPTEX Technologies Inc.
OPTEX Technical Support (800) 877-6656
(East Coast Office)
East Coast: Perry Watkins, Ext. 220
8510 McAlpine Park Dr.
Central U.S.: Jason Kirn, Ext. 201
Suite 108
Support: Refugio Guadaljara, Ext. 202
Charlotte, NC 28211
Note: Walk Test
Power up sensor and wait
10 seconds prior to walk
testing the presence area.
Perform walk test procedure
to verify substantial com-
pliance with ANSI/BHMA
A156.10 section 8.