Auxiliary Circuit Breaker
Auxiliary circuit breaker should be installed near outdoor unit so
that each access is possible. Main/outdoor power supply cable are
connected to upper/lower terminal of auxiliary circuit breaker.
It is necessary that the conduit kit for power supply to the outdoor
unit be installed between auxiliary power S/W and the outdoor
unit. (the conduit kit is optional)
Electrical Work
1
The supply voltage must be the same as the rated voltage of the
air conditioner.
2
Prepare the power souce for exclusive use with the air conditioner.
3
Use 20 amperes time delay fuse or circuit breaker.
MODEL
Power supply
Power cable
Assembly cable
Operating current(C/H)
Starting Current
Power consumption (C/H)
When using the special NFB, use the NFB to bear the capacity of
the air conditioner.
Otherwise, the shot circuit in the NFB may occur.
AD18B1C09
AD26B1C13
208-230V~/60Hz
3G AWG 14
4G AWG 16
8.4A / 7.8A
11.4A / 11.6A
22A
1920W / 1780W
2550W / 2600W
Outdoor unit
The designs and shape are subject to
change according to the model.
31A
I
O
U
NSTALLING THE
UTDOOR
NIT
Distribution
board
Auxiliary
power s/w
41
E-