Siemens SIMATIC S7-1500 Manual page 58

Analog input module ai 4xu/i/rtd/tc st (6es7531-7qd00-0ab0)
Hide thumbs Also See for SIMATIC S7-1500:
Table of Contents

Advertisement

Parameter data records
B.1 Parameter assignment and structure of the parameter data records
Thermal resistor
Pt100 climatic
Ni100 climatic
Pt100 standard
Ni100 standard
Pt500 standard
Pt1000 standard
Ni1000 standard
Pt200 Climatic
Pt500 climatic
Pt1000 climatic
Ni1000 Climatic
Pt200 standard
LG-Ni1000 standard
LG-Ni1000 Climatic
Thermocouple
B
N
E
R
S
J
T
K
Codes for temperature coefficients
The following table lists all temperature coefficients along with their codes for temperature
measurements with the thermal resistors. These codes must be entered in byte 4 of the
corresponding data record.
Table B- 4
Temperature coefficient
Pt xxx
0.003851
0.003916
0.003902
0.003920
Ni xxx
0.006180
0.006720
LG-Ni
0.005000
58
Codes for temperature coefficient
0000 0000
0000 0001
0000 0010
0000 0011
0000 0100
0000 0101
0000 0110
0000 0111
0000 1000
0000 1001
0000 1010
0000 1011
0001 1100
0001 1101
0000 0000
0000 0001
0000 0010
0000 0011
0000 0100
0000 0101
0000 0111
0000 1000
Code
0000 0000
0000 0001
0000 0010
0000 0011
0000 1000
0000 1001
0000 1010
Analog Input Module AI 4xU/I/RTD/TC ST (6ES7531-7QD00-0AB0)