Parameter data records

B.1

Parameter assignment and structure of the parameter data records

The data records of the module have an identical structure, regardless of whether you
configure the module with PROFIBUS DP or PROFINET IO.
Dependencies for configuration with GSD file
When configuring the module with a GSD file, remember that the settings of some
parameters are dependent on each other. The parameters are only checked for plausibility
by the module after the transfer to the module.
The following table lists the parameters that depend on one another.
Table B- 1
Dependencies of parameters for configuration with GSD file
Device-specific parameters (GSD file)
Current limit for wire break
Wire break
Common mode error
Reference junction
Measurement type resistance (4-wire connec-
tion, 3-wire connection, 2-wire connection)
Measurement type thermistor RTD (4-wire con-
nection, 3-wire connection)
Hardware interrupt limits
Fixed reference temperature
Parameter assignment in the user program
The module parameters can be assigned in RUN (for example, measuring ranges of
selected channels can be edited in RUN without having an effect on the other channels).
Parameter assignment in RUN
The WRREC instruction is used to transfer the parameters to the module using data records
0 to 3. The parameters set in STEP 7 do not change in the CPU, which means the
parameters set in STEP 7 are still valid after a restart.
The parameters are only checked for plausibility by the module after the transfer to the
module.
Analog Input Module AI 4xU/I/RTD/TC ST (6ES7531-7QD00-0AB0)
Manual, 09/2016, A5E32366209-AC
Dependent parameters
Only for measurement type current with measuring range 4 to 20 mA.
Only for measurement type resistance, thermistor RTD, thermocouple
TC, voltage with measuring range 1V to 5 V and current with measuring
range 4 to 20 mA.
Only for measuring type voltage, current and thermocouple TC.
Only for measurement type thermocouple TC.
Configurable for even channels (0 and 2) only.
The next odd channel (1 and 3) must be disabled.
Only if hardware interrupts are enabled.
Only if the Reference junction parameter and the Fixed reference tem-
perature value is configured.