Parameter data records

B.1

Parameter assignment and structure of the parameter data records

The data records of the module have an identical structure, regardless of whether you
configure the module with PROFIBUS DP or PROFINET IO.
Dependencies for configuration with GSD file
When configuring the module with a GSD file, remember that the settings of some
parameters are dependent on each other.
The following table lists the parameters that depend on one another.
Table B- 1
Device-specific parameters
(GSD file)
Short circuit to M
Wire break
Substitute value
Parameter assignment in the user program
You have the option to assign module parameters in RUN (e.g., the voltage or current values
of selected channels can be edited in RUN without having an effect on the other channels).
Parameter assignment in RUN
The WRREC instruction is used to transfer the parameters to the module using data records
64 to 67. The parameters set in STEP 7 do not change in the CPU, which means the
parameters set in STEP 7 are still valid after a restart.
The parameters are only checked for plausibility by the module after the transfer to the
module.
Output parameter STATUS
The module ignores errors that occurred during the transfer of parameters with the WRREC
instruction and continues operation with the previous parameter assignment. However, a
corresponding error code is written to the STATUS output parameter.
The description of the WRREC instruction and the error codes is available in the STEP 7
online help.
38
Dependencies of parameters for configuration with GSD file
Dependent parameters
With output type voltage only
With output type current only
Only if Reaction to CPU STOP -> Output substitute value is config-
ured
Analog Output Module AQ 4xU/I HF (6ES7532-5ND00-0AB0)