7. IP Address Setting

7.1

Setting IP address

(1)
Install setting software to computer.
(2)
Connect this product via a LAN straight cable or crossover cable to a PC that has the configuration software
installed in it.
(3)
Take a note of the IP address set in the PC.
PC's IP address
PC's subnet mask
PC's default gateway
(4)
Change the IP address set in the PC according to the IP address (factory setting: 192.168.10.1) set in the product.
IP address set in the product
192.168.10.1
(5)
Use the setting software to set an IP address for EcoWebServer III. Launch the EcoWebServerIII setting software.
[Start menu] > [All Programs] > [Mitsubishi Energy Saving Management Assistance] > [EcoWebServer III
(MES3-255C-EN)]
You can also launch the configuration software by double-clicking the Model: MES3-255C-EN Setting
Software ver3 icon on the desktop.
After a few seconds, the following project management window appears.
:
.
.
:
.
.
:
.
.
IP address to be set to the PC
192.168.10.xx
xx is a value from 2 to 254.
* The upper 3 digits should be consistent
with those for the product.
> Click [Model: MES3-255C-EN Configuration Software ver3].