Specifications; Hardware Specifications - Mitsubishi Electric MES3-255C-EN User Manual

Energy saving data collecting server ecowebserveriii
Table of Contents

Advertisement

9. Specifications

9.1

Hardware specifications

Item
Input power supply
(Entrée d'alimentation électrique)
Input frequency
(Fréquence d'entrée)
Input voltage distortion
(Distorsion)
Consumption VA
(Consommation VA)
Inrush current
(Courant d'afflux)
Allowable momentary power
interruption time
Withstand voltage
Insulation resistance
Noise immunity
Operating ambient temperature
Storage ambient temperature
Operating ambient humidity
Storage ambient humidity
Vibration resistance
Impact resistance
Operating environment
Operating altitude
Installation area
Overvoltage category (*1)
Contamination level (*2)
Mass
Fuse
ERR
Application
terminal
Rated switching
voltage/current
Min. switching load
Life
Ethernet Interface
Transmission method
Cascade connection limit Max. 4 levels (10BASE-T), Max. 2 levels (100BASE-TX)
Max. segment length
Compatible Connector
Functions supported
LAN CH1
client
Server(*3)
Clock
0 to 55ºC
accuracy
25ºC
Backup
Backup data
for
electric
blackout
(*4)
Battery
Type
Initial voltage
Nominal current
AC 100 to 240 V (+10%, -15%)
50/60 Hz (±5%)
Within 5%
19 VA (at AC 110 V), 25 VA (at AC 220 V)
20 A, 8 ms or less(20 ms ou moins (100 V AC ou plus))
20 ms or less (100 V AC or higher)
L,N terminals – extemal case
L,N terminals – output terminals
L,N terminals – CC-Link communication terminals
L,N terminals – extemal case
L,N terminals – output terminals
L,N terminals – CC-Link communication terminals
 By noise simulator with a noise voltage of 1500 Vp-p, a noise width of 1 µs and a noise
frequency of 25 to 60 Hz
 Noise voltage IEC61000-4-4, 2 kV
0 to 55ºC
-25 to +75ºC
5 to 95% RH
5 to 95% RH
-
Conforming to
Intermittent
JIS B 3502,
vibration
IEC 61131-2
Continuous
vibration
Conforming to JIS B 3502, IEC 61131-2 (147 m/s2, 3 times in each XYZ direction)
No corrosive gas
2000 m or below
Inside a board
II or below
2 or below
0.9 kg
Built-in (unchangeable by user)
Off when no power is input, the product is reset, or fuse blows
24 V DC, 0.5 A
5 V DC, 1 mA
Mechanical: 20,000,000 times or more, electrical: 100,000 times or more (at rated
switching voltage/current)
10BASE-T/100BASE-TX
Baseband
100 m
RJ45
Autonegotiation (10BASE-T/100BASE-TX automatically detected)
Auto MDIX function (straight/crossover cable automatically detected)
HTTP (view by web browser), FTP (read time, file transfer),
SMTP (send mail), SNTP (set time)
Ethernet direct: QnA compatible 3E frame (ASCII)
Ethernet / Serial conversion time: A compatible 1C frame format 4 (ASCII)
3 E frame (binary) / 4 E frame (binary)
Per day: -10.89 to +8.64 sec
Per day: -4.32 to +5.25 sec
Backup is made using the battery.
 Clock
 Measurement data for the last 1 hour
Backup is made using nonvolatile memory card.
 Setting values
 Measurement data except the one for the last 1 hour
Lithium manganese dioxide primary battery
3.0 V
1800 mAh
32
Specifications
Constant
Frequency
acceleration
5 to 9 Hz
-
9 to 150 Hz
9.8 m/s2
5 to 9 Hz
-
9 to 150 Hz
4.9 m/s2
Additional difference of ±0.5 seconds can be produced
during outages.
AC 2,210V in 5 seconds
10 MΩ at DC 500 V
Half
Sweep count
amplitude
3.5 mm
10 times in
each X, Y, Z
-
direction
1.75 mm
-
-

Advertisement