Daikin FTXV25AV1B Service Manual page 62

Inverter pair wall mounted type ftxv-ab series
Hide thumbs Also See for FTXV25AV1B:
Table of Contents

Advertisement

Troubleshooting
(8) IPM protection, desynchronizing malfunction, overcurrent of compressor phase current(AP1 below means
control board of outdoor unit)
Main detection points:
Is voltage input within the normal range
If the control board AP1 is well connected with compressor COMP? If they are loosened? If the connection sequence is correct?
Heat exchange of unit is not good (heat exchanger is dirty and unit radiating environment is bad);
If the system pressure is too high?
If the refrigerant charging amount is appropriate?
If coil resistance of compressor is normal? Is compressor coil insulating to copper pipe well?
If the work load of unit is heavy? If radiating of unit is good?
Malfunction diagnosis process:
Measure if the voltage
input is within 180~265V
with AC voltmeter
(see fig 30)
The compressor
is well connected
with mainboard
Heat exchanger is
blocked with dirt?
Check if system pressure
is too high?
Replace outdoor
mainboard AP1
54
Start
N
Y
N
AP1?
Y
Y
N
Y
N
Repair power supply to make
the power voltage normal
N
Adjust it properly
according to wiring
diagram 5.1
N
Clean the heat exchanger
to improve its performance
N
Adjust refrigerant
charging amount
Does the unit
work normally
N
Replace compressor
The unit starts
Restart the unit
operation again
The unit starts
Restart the unit
operation again
The unit starts
Restart the unit
operation again
The unit starts
Restart the unit
operation again
Y
SiK011003
Y
Y
Y
Y
End
Troubleshooting