SEN-600-1 and SEN-600-4 Remote Indoor
Application
The SEN-600-1 and SEN-600-4 remote sensors are
designed to allow remote indoor temperature sensing
in applications with the T600 Series programmable
and non-programmable thermostats and the TEC2100
Metasys® system N2 networked thermostats. The
SEN-600-1 and SEN-600-4 contain an integral sensor
and circuitry to interface with the T600 and TEC2100
thermostats. Additionally, the SEN-600-4 has an
override button and Light-Emitting Diode (LED)
indicator to enable and indicate occupancy override
from the remote sensor. Up to three remote sensors
can be wired together for averaging.
Note: The SEN-600-4 remote indoor sensor is only
intended for use with programmable T600 Series
thermostats. Additionally, if the SEN-600-4 is used
with a T600 non-programmable thermostat, the LED
does not light up to indicate occupancy status.
Mounting
Prior to installing the sensor, install the T600 or
TEC2100 thermostat following the installation
instructions provided with the thermostat.
Location Considerations
Locate the sensors as follows:
on a partitioning interior wall, and approximately
1.5 m (5 ft) above the floor in a location of average
temperature
away from direct sunlight, radiant heat, outside
walls, behind doors, air discharge grills, stairwells,
or outside doors
away from steam or water pipes, warm air stacks,
unheated/uncooled areas, or sources of electrical
interference
©
2003 Johnson Controls, Inc.
Part No. 24-9954-7, Rev. —
Temperature Sensors
Installation
Dimensions
To install the sensor:
1. Remove the security screw on the bottom of the
2. Unlock the Printed Circuit Board (PCB) by
3. Pull out approximately 152 mm (6 in.) of wires
4. Align the base on the wall, and using the base as
5. Use the supplied anchors and screws for mounting
6. Position base on the wall, insert screws through
7. Swing the sensor's PCB back to the right to close.
Installation Instructions
Issue Date September 23, 2003
86
3.38
Figure 1: Sensor Dimensions (mm/in.)
sensor cover using a Phillips-head screwdriver.
Open the thermostat by pulling on the bottom side
of the sensor cover (see Figure 2).
carefully pressing the locking tabs to the right.
Open the sensor's PCB to the left (see Figure 3).
from the wall and insert the cable through the hole
in the base.
a template, mark the location of the two mounting
holes on the wall. Confirm the sensor base is
installed with the proper side up.
on drywall or plaster. Drill two 4.7 mm (3/16 in.)
holes at the marked locations and tap nylon
anchors flush to wall surface (see Figure 4).
mounting base, and fasten into wall anchors. Do
not overtighten screws.
Gently press on the PCB to secure the locking tab.
125
4.94
29
1.13
1
www.johnsoncontrols.com

Advertisement

loading

Summary of Contents for Johnson Controls SEN-600-1

  • Page 1 Issue Date September 23, 2003 SEN-600-1 and SEN-600-4 Remote Indoor Temperature Sensors Application Installation The SEN-600-1 and SEN-600-4 remote sensors are Dimensions designed to allow remote indoor temperature sensing in applications with the T600 Series programmable and non-programmable thermostats and the TEC2100 Metasys®...
  • Page 2 Table 1: Switch Positions for Single or Multiple Sensor Installations Number of Sensors Switch 1 Switch 2 Figure 4: Mounting the Sensor Base 1 Sensor 2 Sensor 3 Sensor SEN-600-1 and SEN-600-4 Remote Indoor Temperature Sensors Installation Instructions...
  • Page 3 SEN-600-4 is not used. Additionally, when using the SEN-600-4 remote indoor sensor with a non-programmable model of the T600, the LED will not light to indicate occupancy status. Figure 5:Wiring Diagrams SEN-600-1 and SEN-600-4 Remote Indoor Temperature Sensors Installation Instructions...
  • Page 4: Troubleshooting

    The LED does not indicate occupancy the SEN-600-4 is connected is not a status on non-programmable T600 programmable model. models (there is no auxiliary contact at the thermostat). Replace the T600 with a programmable model. SEN-600-1 and SEN-600-4 Remote Indoor Temperature Sensors Installation Instructions...
  • Page 5: Technical Specifications

    The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.

This manual is also suitable for:

Sen-600-4