Conair EP2 series User Manual page 25

Portable chillers. portable and remote condenser chillers 4 to 43 tons ep2
Hide thumbs Also See for EP2 series:
Table of Contents

Advertisement

Table 14 – Standard Controller Modbus RTU Option Parameters (continued)
Register
4011
Low Alarm Delay
4012
High Alarm Delay
4013
Temperature Display Units
4015
Brownout Enabled
4024
Remote Setpoint Enabled
4025
Autostart Enabled
4027
Communication BAUD Rate
4028
MODBUS Identification
4030
SPI Communications Address
4033
Compressor 2 Enabled
4038
Hot Gas Bypass PID Output
4039
MODBUS Command
8000
Freezestat Temperature (°C)
8002
Supply Fluid Temperature (°C)
8004
Return Fluid Temperature (°C)
8010
Low Temperature Deviation (°C)
8012
High Temperature Deviation (°C)
8014
Low Setpoint Limit Temperature (°C)
8016
High Setpoint Limit Temperature (°C)
8018
Supply Temperature Retransmit Range Low (°C)
8020
Supply Temperature Retransmit Range High (°C)
8022
Low Temperature Safety – User Set (°C)
8024
High Temperature Safety – User Set (°C)
8026
Proportional Band (°C)
8052
Pump Running Hours
8054
Setpoint Temperature (°C)
8056
Low Temperature Safety – Factory Set (°C)
8058
High Temperature Safety – Factory Set (°C)
8060
Negative Compressor 1 Spread (°C)
8062
Negative Compressor 2 Spread (°C)
8064
Positive Compressor 1 Spread (°C)
8066
Positive Compressor 2 Spread (°C)
8068
Freezestat Limit Temperature (°C)
8070
Supply Temperature Input Offset
8072
Return Temperature Input Offset
8074
Remote Setpoint Temperature Input Offset
8078
Freezestat Temperature Input Offset
8080
Remote Setpoint Limit Temperature (°C)
8082
Remote Setpoint High Temperature Limit (°C)
8110
Compressor 1 Running Hours
8112
Compressor 2 Running Hours
Note: All temperatures are in °C regardless of unit display configuration.
Description
Read/Write
Format
R
Integer
R
Integer
R
Integer
R
Integer
R
Integer
R
Integer
R/W
Integer
R/W
Integer
R/W
Integer
R
Integer
R
Integer
R/W
Integer
R
Floating Point Error Hi = 9.9E05, Error Low = -9.9E05
R
Floating Point Error Hi = 9.9E05, Error Low = -9.9E05
R
Floating Point Error Hi = 9.9E05, Error Low = -9.9E05
R/W
Floating Point
R/W
Floating Point
R
Floating Point
R
Floating Point
R
Floating Point
R
Floating Point
R/W
Floating Point
R/W
Floating Point
R/W
Floating Point
R
Floating Point
R/W
Floating Point
R
Floating Point
R
Floating Point
R
Floating Point
R
Floating Point
R
Floating Point
R
Floating Point
R
Floating Point
R
Floating Point
R
Floating Point
R
Floating Point
R
Floating Point
R
Floating Point
R
Floating Point
R
Floating Point
R
Floating Point
19
Notes
0 = °F, 1 = °C
0 = Disabled, 1 = Enabled
0 = Disabled, 1 = Enabled
0 = Disabled, 1 = Enabled
0 = 1200, 1 = 2400, 2 = 4800, 3 = 9600
0 = Disabled, 1 = Enabled
-100 to 100 PID algorithm output
0 = Do Nothing, 1 = Start, 2 = Stop