in the Set Point display until the desired value shows.
Press the Start button to enter the new value. Press
the Stop button to cancel and revert to the previous
value.
There is a Master Reset function to restore all User
menu parameters to their factory default values. The
unit must be in a stopped state for this function to
work. To initiate a Master Reset press and hold the

Table 11 - Controller Program Menu

Item Name
Alarm delay for high deviation alarm
Alarm delay for low deviation
Alarm deviation alarm delay after
start
Alarm output
Autostart enable
Brownout monitor
Communications Baud Rate
Communications Modbus ID
Communications SPI Address
Communications type
1
Compressor 1 negative spread
Compressor 1 positive spread
Compressor 2 enabled
Compressor 2 negative spread
Compressor 2 positive spread
Derivative
Display units
Freezestat limit
High deviation alarm limit
Integral
Low deviation alarm limit
Panel temperature alarm
Panel temperature readout
Proportional band
Remote Setpoint High limit
1
Remote Setpoint Low limit
1
Remote Setpoint Enable
1
Retransmit Range High
1
Retransmit Range Low
1
User High Safety limit
User Low Safety limit
User password
Optional, requires additional hardware to be functional.
1
Default
Item Code
Value
AdH
30
AdL
30
ADS
30
AdO
DI S
AS E
E nA
br n
E nA
1
bAU
96
1
i d
1
1
S PA
32
COt
OF F
nS 1
4
PS 1
2
CO2
DI S
nS 2
5
PS 2
3
dE r
3
Unt
F
F S L
40
HI d
10
I nt
25
L od
10
PAe
E nA
Pt e
-
bnd
8
r S H
65
r S L
20
r S E
DI S
r E H
150
r E L
0
HS U
140
L S U
10
UPA
000
Alarm Silence/Reset button and Stop button
simultaneously for 10 consecutive seconds until
"PRG" shows on the Set Point display and "RSt"
shows on the Process display. Release all buttons
and press the Start button within 10 seconds. Failure
to push the Start button within 10 seconds aborts
the Master Reset.
0 to 60 minutes (10 to 60 minutes on program versions prior to version 1.33)
0 to 60 minutes (10 to 60 minutes on program versions prior to version 1.33)
0 to 30 minutes on program version 1.33 and later only
Disabled
(DI S
) or Enabled
(E
Disabled
(DI S
) or Enabled
(E
Disabled
(DI S
) or Enabled
(E
12 to 96
1 to 247
32 to 63
OFF, Retransmit
(r E t
), SPI
(S PI
1 to 10
1 to 10
Disabled
(DI S
) or Enabled
(E
1 to 10
1 to 10
0 to 200
F to C
-50 to 40
5 to 100 degrees about set point
1 to 800
5 to 100 degrees below set point
Disabled
(DI S
) or Enabled
(E
Display only
1 to 300
Between
and 999
r S L
Between -99 and
r S H
Disabled
(DI S
) or Enabled
(E
Between 999 and
r E L
Between -99 and
r E H
Between factory low and high limits
Between factory low and high limits
0 to 999
16
Range
nA) on program versions 1.33 and later only
nA)
nA)
), ModBus
(bUS
), Handheld Remote
nA)
nA)
nA)
(Ha
n)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents