Trip Code
Trip
Number
EEF
31
Failure of internal EEPROM
PH
32
Phase loss
rS
Stator resistance measurement
33
failure
trxx
User trips where xx is the user trip
40-99
number
F.bus
180
Field bus disconnection whilst in use
C.Err
182
Quickey memory corrupt
C.dat
183
Quickey with no data
C.Acc
185
Quickey write fail
C.rtg
186
Quickey voltage rating change
O.Ld2
+28V serial communications power
188
supply overload
O.cL††
189
Current loop input overload
Motor runs unstable
* The Enable/Reset terminal will not reset an O.Ld1 trip. Use the Stop/Reset key.
** These trips cannot be reset for 10 seconds.
Commander SE Size 4 temperature exceeds
See information under terminal 5 on page 37.
††
If any of the above trips persist, please consult a Drive Centre.
OU - Overvoltage trip levels:
200V units - 420Vdc
400V units - 830Vdc
Braking levels:
200V units - 390Vdc
400V units - 780Vdc
UU - Undervoltage trip levels:
200V units - 180Vdc
400V units - 400Vdc
Reset from UU - Under voltage trip:
200V units - 235Vdc
400V units - 460Vdc
These are the absolute minimum DC voltages that the drive can be supplied by.
NOTE
Commander SE User Guide
Issue Number 8
Condition
Possible loss of parameter values
Corruption due to severe electrical noise
Set default parameters (see parameter 29)
One of the input phases has become
disconnected from the drive. (This applies to
200V/400V three phase units only, not dual
rated units).
Motor cable disconnected during measurement
Motor too small for drive
See parameter 38 for more details
Bad connection or memory corrupt
New / empty Quickey being read
Quickey / drive software compatibility issue
Bad connection or faulty Quickey
Already programmed Quickey read by drive of
different rating
Overload of more than 110 mA or short circuit
on +28V serial communications power supply
Input current exceeded 25mA
Motor or motor connections changed. Check
motor connections and
re-autotune drive to motor (see parameter 38)
Table 8.1 Trip Codes